Mounting and wiring
KL3102, KL3112, KL3122
25
Version: 3.2
3.5
KL3102 - Connection and LED description
WARNING
Risk of injury through electric shock and damage to the device!
Bring the Bus Terminal system into a safe, voltage-free state before starting mounting, disassembly or
wiring of the Bus Terminals!
Fig. 13: KL3102
KL3102 - Connection
Terminal point
No.
Comment
+Input 1
1
+ Input 1
-Input 1
2
- Input 1
GND
3
Internal ground (internally connected to terminal point 7)
Shield
4
PE contact (internally connected to terminal point 8)
+Input 2
5
+ Input 2
-Input 2
6
- Input 2
GND
7
Internal ground (internally connected to terminal point 3)
Shield
8
PE contact (internally connected to terminal point 4)
KL3102 - LEDs
LED
Color Description
Run LED1
Run LED2
green On: Normal operation
Off: Watchdog timer overflow has occurred. If no process data is transmitted to the Bus Coupler
for 100 ms, the green LEDs go out