Product overview
KL304x, KL305x
12
Version: 4.0
◦ On: The limit stop of the A/D converter has been reached. The current is greater than 21.5 mA.
◦ Off: Normal operation
Process data output format
In the delivery state the process data are shown in two's complement form (integer -1 corresponds to
0xFFFF). Other presentation types can be selected via the feature register (
representation, Siemens output format).
Measured value
Output
KL304x
KL305x
dec
hex
0 mA
4 mA
0
0x0000
10 mA
12 mA
16383
0x3FFF
20 mA
20 mA
32767
0x7FFF
Calculation of process data
The terminal continuously takes measured values and stores the raw values of its A/D converter in register
(RAM ). The calculation of the correction with the calibration values takes place after each
sampling of the analog signal. This is followed by manufacturer and user scaling:
The process data that are transferred to the Bus Coupler are calculated using the following equations:
Y_a = (B_a + X_adc) * A_a
Y_aus = Y_a
(1.0)
Neither user nor manufacturer scaling is active.
Y_1 = B_h + A_h * Y_a
Y_aus = Y_1
(1.1)
Manufacturer scaling active: (Default setting)
Y_2 = B_w + A_w * Y_a
Y_aus = Y_2
(1.2)
User scaling active
Y_1 = B_h + A_h * Y_a
Y_2 = B_w + A_w * Y_1
Y_aus = Y_2
(1.3)
(1.4)
Manufacturer and user scaling active
Key
Name
Name
Register
X_adc
Output value of the A/D converter
-
Y_aus
Process data for controller
-
B_a
Vendor calibration: Offset
A_a
Vendor calibration: Gain
B_h
Manufacturer scaling: Offset
A_h
Manufacturer scaling: Gain
B_w
User scaling: Offset
A_w
User scaling: Gain
The equations of the straight line are enabled via register
.
Fig. 4: KL304x, KL305x - Data flow