CoE parameters
EPP3752-0000
37
Version: 1.2
Index 8020 AI Settings Ch.3
Index (hex) Name
Meaning
Data type
Flags
Default
8020:0
AI Settings Ch.3
UINT8
RO
0x1A (26
dec
)
8020:06
Enable filter
Activates the filter.
BOOLEAN
RW
0x00 (0
dec
)
8020:15
Filter settings
This object determines the filter settings of all chan-
nels of the module when it is activated via
Enable fil-
ter
index 0x80n0:06.
UINT16
RW
0x0002 (2
dec
)
0
FIR
2
IIR1
3
IIR2
4
IIR3
5
IIR4
6
IIR5
7
IIR6
8
IIR7
9
IIR8
8020:19
Range
Setting the measuring range:
• 0
dec
: +-2G
• 1
dec
: +-4G
• 2
dec
: +-8G
• 3
dec
: +-16G
UINT16
RW
0x0000 (0
dec
)
8020:1A
Presentation
Representation of the data
• 0
dec
: Raw values
• 1
dec
: milli G (mG)
UINT16
RW
0x0001 (1
dec
)
Index 8030 AI Settings Ch.4
Index (hex) Name
Meaning
Data type
Flags
Default
8030:0
AI Settings Ch.4
UINT8
RO
0x11 (21
dec
)
8030:06
Enable filter
Activates the filter.
BOOLEAN
RW
0x00 (0
dec
)
8030:15
Filter settings
This object determines the filter settings of all chan-
nels of the module when it is activated via
Enable fil-
ter
index 0x80n0:06.
UINT16
RW
0x0002 (2
dec
)
0
FIR
2
IIR1
3
IIR2
4
IIR3
5
IIR4
6
IIR5
7
IIR6
8
IIR7
9
IIR8
8030:19
Range
Setting the measuring range:
• 0
dec
: +-2G
• 1
dec
: +-4G
• 2
dec
: +-8G
• 3
dec
: +-16G
UINT16
RW
0x0000 (0
dec
)
8030:1A
Presentation
Representation of the data
• 0
dec
: Raw values
• 1
dec
: milli G (mG)
UINT16
RW
0x0001 (1
dec
)
Содержание EPP3752-0000
Страница 1: ...Documentation EN EPP3752 0000 2 x 3 axis accelerometers 2022 09 19 Version 1 2...
Страница 2: ......
Страница 4: ...Table of contents EPP3752 0000 4 Version 1 2...
Страница 55: ......