Commissioning/Configuration
EPP1xxx
80
Version: 1.4
5.6
Restoring the delivery state
The CoE object
Restore default parameters, Subindex 001
can be selected in the TwinCAT System
Manager (Config mode) in order to restore the delivery state of the back-up objects for the EPPxxxx Boxes.
Fig. 13: Selecting the PDO restore default parameter
Double-click on SubIndex
001
to enter the Set Value dialog. Enter the value
1684107116
in the field
Dec
or
alternatively the value
0x64616F6C
in the field
Hex
and confirm with OK.
All backup objects are reset to the delivery state.
Fig. 14: Entering a restore value in the Set Value dialog
Alternative restore value
With some older modules the backup objects can be changed with an alternative restore value:
Decimal value: 1819238756
Hexadecimal value: 0x6C6F6164
An incorrect entry for the restore value has no effect.