Commissioning and configuration
EP4374
39
Version: 2.3
Index 8030 AO Settings Ch.4
Index (hex) Name
Meaning
Data type
Flags
Default
8030:0
AO Settings Ch.4
Maximum subindex
UINT8
RO
0x16 (22
dec
)
8030:01
Enable user scale
0
bin
User scaling not active
BOOLEAN
RW
0x00 (0
dec
)
1
bin
User scaling active
8030:02
Presentation
0
dec
Signed presentation
The output value range 0x7pp1:11 is shown as
16 bit signed integer. For unipolar terminals
(0-10V or 0-20 mA) the negative range is set to
zero.
BIT3
RW
0x00 (0
dec
)
1
dec
Unsigned presentation
The output value range 0x7pp1:11 is shown as
16 bit unsigned integer. Negative values are not
possible.
2
dec
Absolute value with MSB as sign
Signed amount representation is active.
3
dec
Absolute value
The absolute value of the signed representation
is formed.
8030:05
Watchdog
0
dec
Default watchdog value
The default value (0x8pp0:13) is active.
BIT2
RW
0x00 (0
dec
)
1
dec
Watchdog ramp
The ramp (0x8pp0:14) for moving to the default
value ((0x8pp0:13)) is active.
2
dec
Last output value
In the event of an error (triggering of the watch-
dog) the last process data is output.
8030:07
Enable user calibra-
tion
0
bin
User calibration not active
BOOLEAN
RW
0x00 (0
dec
)
1
bin
User calibration active
8030:08
Enable vendor cali-
bration
0
bin
Manufacturer calibration not active
BOOLEAN
RW
0x01 (1
dec
)
1
bin
Vendor calibration active
8030:11
User scale offset
User scaling: Offset
INT16
RW
0x0000 (0
dec
)
8030:12
User scale gain
User scaling: Gain
This is the user scaling gain. The gain is represented in
fixed-point format, with the factor 2
-16
. The value one cor-
responds to 65535 (0x00010000).
INT32
RW
0x00010000
(65536
dec
)
8030:13
Default output
Default output value
INT16
RW
0x0000 (0
dec
)
8030:14
Default output ramp
This value defines the ramps for the ramp-down to the
default value. The value is specified in digits/ms.
If the entry is 100 and the default value 0, for example, it
takes 327 ms (32767/100) for the output value to change
from the maximum value (32767) to the default value in
the event of a fault.
UINT16
RW
0xFFFF
(65535
dec
)
8030:15
User calibration offset User calibration: Offset
INT16
RW
0x0000 (0
dec
)
8030:16
User calibration gain
User calibration: Gain
UINT16
RW
0x4000
(16384
dec
)
Index F800 AIAO Range settings
Index (hex) Name
Meaning
Data type
Flags
Default
F800:0
AIAO Range settings
Maximum subindex
UINT8
RO
0x04 (4
dec
)
F800:01
Input type Ch1
Input signal range for channel 1
UINT16
RW
0x0000 (0
dec
)
0
dec
-10…+10 V
1
dec
0...20 mA
2
dec
4...20 mA
3
dec
0...10 V
F800:02
Input type Ch2
Input signal range for channel 2 (values see channel 1)
UINT16
RW
0x0000 (0
dec
)
F800:03
Output type Ch3
Output signal range for channel 3
UINT16
RW
0x0000 (0
dec
)
0
dec
-10…+10 V
1
dec
0...20 mA
2
dec
4...20 mA
3
dec
0...10 V
F800:04
Output type Ch4
Output signal range for channel 4 (values see channel 3) UINT16
RW
0x0000 (0
dec
)
Содержание EP4374