Commissioning/Configuration
EP4174-0002
50
Version: 1.1.0
Index 8020 AO settings Ch.3
Index (hex) Name
Meaning
Data type
Flags
Default
8020:0
AO settings Ch.3
Maximum subindex
UINT8
RO
0x16 (22
dec
)
8020:01
Enable user scale
This entry activates the scaling for 0x8pp0:11 and
0x8pp0:12.
BOOLEAN
RW
0x00 (0
dec
)
8020:02
Presentation
0
Signed presentation
The output value range 0x7pp1:11 is shown as
16 bit signed integer. For unipolar terminals
(0-10V or 0-20 mA) the negative range is set to
zero.
BIT3
RW
0x00 (0
dec
)
1
Unsigned presentation
The output value range 0x7pp1:11 is shown as
16 bit unsigned integer. Negative values are not
possible.
2
Absolute value with MSB as sign
Signed amount representation is active.
3
Absolute value
The absolute value of the signed representation is
formed.
8020:05
Watchdog
0
Default watchdog value
The default value (0x8pp0:13) is active.
BIT2
RW
0x00 (0
dec
)
1
Watchdog ramp
The ramp (0x8pp0:14) for moving to the default
value ((0x8pp0:13)) is active.
2
Last output value
In the event of an error (triggering of the watchdog)
the last process data is output.
8020:07
Enable user calibra-
tion
Enables user calibration
BOOLEAN
RW
0x00 (0
dec
)
8020:08
Enable vendor cali-
bration
Enable vendor calibration
BOOLEAN
RW
0x01 (1
dec
)
8020:11
User scale offset
User scaling: Offset
INT16
RW
0x0000 (0
dec
)
8020:12
User scale gain
User scaling: Gain.
The gain is represented in fixed-point format, with the
factor 2
-16
. The value one corresponds to 65535
(0x00010000).
INT32
RW
0x00010000
(65536
dec
)
8020:13
Default output
Default output value
INT16
RW
0x0000 (0
dec
)
8020:14
Default output ramp
This value defines the ramps for the ramp-down to the
default value. The value is specified in digits / ms.
If the entry is 100 and the default value 0, for example, it
takes 327 ms (32767/100) for the output value to change
from the maximum value (32767) to the default value in
the event of a fault.
UINT16
RW
0xFFFF
(65535
dec
)
8020:15
User calibration offset User calibration: Offset
INT16
RW
0x0000 (0
dec
)
8020:16
User calibration gain
User calibration: Gain
UINT16
RW
0x4000
(16384
dec
)