Product overview
ELX1052, ELX1054 and ELX1058
15
Version: 2.0.0
2.4
Technical data
Technical data
ELX1052-0000
ELX1054-0000
ELX1058-0000
Technology
NAMUR
Number of inputs
2
4
8
Signal type
binary/current
Specification
NAMUR DC switching amplifier (IEC 60947-5-6)
Connection technology
2-wire
“0“ signal current
≤ 1.2 mA
“1“ signal current
≥ 2.1 mA
Switching hysteresis
typ. 200 µA
typ. 200 µA
typ. 300 µA
Switching frequency
max. 50 Hz
(duty cycle 50%)
max. 5 kHz
(duty cycle 50%)
max. 5 kHz
(duty cycle 50%)
Open circuit voltage
typ. 8.2 V
Current limitation
> 8.2 mA typ.
> 7 mA typ.
Short circuit detection
> 6.3 mA typ.
Distributed Clocks
-
Supply voltage electronics
via E-Bus (5 V
DC
) and Power Contacts (24 V
DC
Ex, feeding by
ELX9560)
Current consumption from the E-Bus
typ. 50 mA
typ. 70 mA
Current consumption from the Power
Contacts
typ. 10 mA + load
typ. 15 mA + load
Electrical isolation
1500 V (E-Bus / field potential)
Bit width in the process image
2 x 2 bit
4 x 2 bit + 4 bit input
type NC status
8 x 2 bit
Weight
approx. 45 g
approx. 50 g
approx. 65 g
Permissible ambient temperature range
during operation
-25°C ... + 60°C
Permissible ambient temperature range
during storage
-40°C ... + 85°C
Permissible relative humidity
95 %, no condensation
Permissible air pressure
(operation, storage, transport)
800 hPa to 1100 hPa
(this corresponds to a height of approx. -690 m to 2000 m over
sea level assuming an international standard atmosphere)
Dimensions (W x H x D)
ca. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
Mounting
on 35 mm mounting rail conforms to EN 60715
Vibration/shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27
EMC immunity/emission
conforms to EN 61000-6-2 / EN 61000-6-4
Protect. class
IP20
Permissible installation position
Installation position and minimum distances [
Approvals / markings
CE, UL, ATEX, IECEx, cFMus
CE, ATEX, IECEx