Operation
EL9930
14
Version: 1.2.0
CAUTION
Note the specified environmental conditions
Please ensure that the EL components are only transported and stored under the specified environmental
conditions (see technical data).
3.1.4
Mechanical installation
WARNING
Risk of injury!
Bring the bus system into a safe, de-energized state before starting installation, disassembly or wiring of
the devices!
3.1.4.1
Control cabinet / terminal box
For operation the EL9930 terminals must be installed in a control cabinet or terminal box with a minimum
protection class of IP54 according to IEC 60529.
3.1.4.2
Installation position and minimum distances
For the prescribed installation position the mounting rail is installed horizontally and the mating surfaces of
the EL/KL terminals point toward the front (see illustration below). The terminals are ventilated from below,
which enables optimum cooling of the electronics through convection. The direction indication “down”
corresponds to the direction of positive acceleration due to gravity.
Fig. 6: Installation position and minimum distances
In order to ensure optimum convection cooling, the distances to neighboring devices and to control cabinet
walls must not be smaller than those shown in the diagram.