Object description and parameterization
EL72x1-901x
193
Version: 1.9
Index 8011 DRV Motor Settings
Index (hex) Name
Meaning
Data type
Flags
Default
8011:0
DRV Motor Settings
Maximum subindex
UINT8
RO
0x2D (45
dec
)
8011:11*
Max current
Peak current
Unit
: mA
The adjustable motor current values can be interpreted
as peak values or rms values. The feature bit (
Peak value → Bit 0 = 0 (default with EL7201-001x)
Rms value → Bit 0 = 1 (default with EL7211-001x)
This value is affected by automatic scanning.
(see
Automatic scanning of the electronic type plates
UINT32
RW
0x00001770
(6000
dec
)
8011:12*
Rated current
Rated current
Unit
: mA
The adjustable motor current values can be interpreted
as peak values or rms values. The feature bit (
Peak value → Bit 0 = 0 (default with EL7201-001x)
Rms value → Bit 0 = 1 (default with EL7211-001x)
This value is affected by automatic scanning.
(see
Automatic scanning of the electronic type plates
UINT32
RW
0x000003E8
(1000
dec
)
8011:13*
Motor pole pairs
Number of pole pairs
This value is affected by automatic scanning.
(see
Automatic scanning of the electronic type plates
UINT8
RW
0x03 (3
dec
)
8011:15*
Commutation offset
Commutation offset (between electrical zero position
and mechanical single-turn zero position)
Unit
:
This value is affected by automatic scanning.
(see
Automatic scanning of the electronic type plates
INT16
RW
0x0000 (0
dec
)
8011:16*
Torque constant
Torque constant
Unit
: mNm / A
This value is affected by automatic scanning.
(see
Automatic scanning of the electronic type plates
UINT32
RW
0x00000000
(0
dec
)
8011:18*
Rotor moment of iner-
tia
Mass moment of inertia of the motor
Unit
: g cm^2
This value is affected by automatic scanning.
(see
Automatic scanning of the electronic type plates
UINT32
RW
0x00000000
(0
dec
)
8011:19*
Winding inductance
Inductance
Unit
: 0.1 mH
This value is affected by automatic scanning.
(see
Automatic scanning of the electronic type plates
UINT16
RW
0x000E (14
dec
)
8011:1B*
Motor speed limitation Velocity limitation
Unit
: rpm
This value is affected by automatic scanning.
(see
Automatic scanning of the electronic type plates
UINT32
RW
0x00040000
(262144
dec
)
*) see index 9009 FB OCT Nameplate
Содержание EL72 1-901 Series
Страница 1: ...Documentation EL72x1 901x Servo Motor Terminals with OCT and STO 50 V DC 1 9 2020 02 18 Version Date...
Страница 2: ......
Страница 6: ...Table of contents EL72x1 901x 6 Version 1 9...
Страница 20: ...Product overview EL72x1 901x 20 Version 1 9 2 3 Technical data...
Страница 49: ...Installation EL72x1 901x 49 Version 1 9 Fig 36 Shield busbar Fig 37 Shield busbar clamp...
Страница 86: ...Commissioning EL72x1 901x 86 Version 1 9 Fig 88 Incorrect driver settings for the Ethernet port...
Страница 140: ...Commissioning EL72x1 901x 140 Version 1 9 0hex 80hex Fault reset 6hex Shutdown 7hex Switch on Fhex Enable operation...
Страница 141: ...Commissioning EL72x1 901x 141 Version 1 9 Fig 176 DS402 State Machine...
Страница 150: ...Commissioning EL72x1 901x 150 Version 1 9 Fig 184 Touch Probe inputs...
Страница 172: ...Commissioning EL72x1 901x 172 Version 1 9 Fig 207 Process Data tab SM2 EL72x1 0010 default...
Страница 256: ...Appendix EL72x1 901x 256 Version 1 9 9 5 Certificates Fig 233 EL72x1 9014_Certificate...