Commissioning
EL3182
88
Version: 1.2
Index 0xA0n0 HART Diag data (n=8: Channel 1, n=9: Channel 2)
Index
(hex)
Name
Meaning
Data type
Flags Default
A0n0:0
HART Diag data
Maximum subindex
UINT8
RO
0x04 (4
dez
)
A0n0:01
RcvFrameError
Received Frame Error Counter
UINT8
RO
0x00 (0
dez
)
A0n0:02
RcvCheckSumErr
or
Received CheckSum Error Counter
UINT8
RO
0x00 (0
dez
)
A0n0:03
RcvTimeOutError Received Timeout Error Counter
UINT8
RO
0x00 (0
dez
)
A0n0:04
DataExchState
DataExchange State
UINT8
RO
0x00 (0
dez
)
Index 0xF900 Info data
Index
(hex)
Name
Meaning
Data type
Flags Default
F900:0
Info data
Maximum subindex
UINT8
RO
0x01 (1
dez
)
F900:01
HART Version
Master HART Version
UINT16
RO
-
5.3.5
Command objects
Index 0x60n0 HART Command 3 (n=8: Channel 1, n=9: Channel 2)
Index
(hex)
Name
Meaning
Data type
Flags Default
60n0:0
HART Cmd3
Maximum subindex
UINT8
RO
0x0D (13
dez
)
60n0:01
Field Device
Status
Represent the current state of the
slave
UINT8
RO
0x00 (0
dez
)
60n0:02
Cyclic Frame Cnt Cyclic Frame Counter
UINT8
RO
0x00 (0
dez
)
60n0:05
Primary Variable
Units Code
Primary Variable Units Code (refer to
HART 'Common Table Specification')
UINT8
RO
0x00 (0
dez
)
60n0:06
Secondary
Variable Units
Code
Secondary Variable Units Code (refer
to HART 'Common Table
Specification')
UINT8
RO
0x00 (0
dez
)
60n0:07
Tertiary Variable
Units Code
Tertiary Variable Units Code (refer to
HART 'Common Table Specification')
UINT8
RO
0x00 (0
dez
)
60n0:08
Quaternary
Variable Units
Code
Quaternary Variable Units Code (refer
to HART 'Common Table
Specification')
UINT8
RO
0x00 (0
dez
)
60n0:09
Primary Variable
Loop Current
Primary Variable Loop Current (units of
milli-amperes)
REAL32
RO
0x00000000
(0
dez
)
60n0:0A
Primary Variable
Primary Variable (vendor specific)
REAL32
RO
0x00000000
(0
dez
)
60n0:0B
Secondary
Variable
Secondary Variable (vendor specific)
REAL32
RO
0x00000000
(0
dez
)
60n0:0C
Tertiary Variable
Tertiary Variable (vendor specific)
REAL32
RO
0x00000000
(0
dez
)
60n0:0D
Quaternary
Variable
Quaternary Variable (vendor specific)
REAL32
RO
0x00000000
(0
dez
)
Содержание EL3182
Страница 2: ......
Страница 46: ...Commissioning EL3182 46 Version 1 2 Fig 43 Incorrect driver settings for the Ethernet port...
Страница 57: ...Commissioning EL3182 57 Version 1 2 Fig 62 EtherCAT terminal in the TwinCAT tree left TwinCAT 2 right TwinCAT 3...
Страница 94: ...Commissioning EL3182 94 Version 1 2 Index 0x1C32 SM output parameter...