Device
XML revision in the configuration
Serial number of the component
BK1150
from BK1150-0000-0016
from firmware 01: xxxx01yy
CU1128
from CU1128-0000-0000
from firmware 00: xxxx00yy
EK1100
from EK1100-0000-0017
from firmware 06: xxxx06yy
EK1101
from EK1101-0000-0017
from firmware 01: xxxx01yy
EK1501
from EK1501-0000-0017
from firmware 01: xxxx01yy
EK1501-0010
from EK1501-0010-0017
from firmware 02: xxxx02yy
EK1122
from EK1122-0000-0017
from firmware 01: xxxx02yy
EK1521
from EK1521-0000-0018
from firmware 03: xxxx03yy
EK1541
from EK1541-0000-0016
from firmware 01: xxxx01yy
EK1561
from EK1561-0000-0016
from firmware 01: xxxx01yy
EK1521-0010
from EK1521-0010-0018
from firmware 03: xxxx03yy
EK1814
from EK1814-0000-0016
from firmware 00: xxxx00yy
Table 1: DC support from rev/firmware version
To ensure that TwinCAT uses such a component as DC reference clock, a manual intervention during the
configuration setup is required, as shown here using the EK1100 as an example.
The checkboxes “
Cyclic Mode Enable”
and “
Use as potential Reference Clock”
must be set.
Fig. 15: TwinCAT setting for using this component as reference clock
Activation of Distributed Clocks support
The (synchronization) procedure described here is only successful for the components described
above. The checkboxes can be set for other components, too, although the hardware does not sup-
port this function, unless specified in the respective documentation.
In particularly, please note that after commissioning the component may not be replaced with a pre-
vious version without DC support.
Содержание EK18 Series
Страница 1: ...Documentation EK18xx EtherCAT Bus Coupler 2 2 03 04 2019 Version Date ...
Страница 2: ......
Страница 6: ...Table of contents EK18xx 6 Version 2 2 ...
Страница 44: ...Parameterization and commissioning EK18xx 44 Version 2 2 6 2 2 EK1818 Fig 37 TwinCAT tree EK1818 ...
Страница 47: ...Parameterization and commissioning EK18xx 47 Version 2 2 6 2 3 EK1828 Fig 40 TwinCAT tree EK1828 ...
Страница 49: ...Parameterization and commissioning EK18xx 49 Version 2 2 Fig 42 Extent of process data EK1828 TwinCAT ...