Configuration
CX51x0
65
Version: 2.8
NOTE
Unwanted restart
The watchdog restarts the Embedded PC as soon as the time set for nWatchdogTimeS elapses.
Be aware of this behavior and disable the watchdog if you use breakpoints, carry out a PLC reset or an
overall reset, stop TwinCAT, switch to config mode or activate the configuration.
Requirements:
• Tc2_System library.
• TwinCAT v3.1.0
• A previously created PLC project in TwinCAT.
Locating the function block in TwinCAT:
1. Double-click on
Tc2_System
in the tree view under
PLC > PLC project > References
.
The Library Manager appears.
2. Under
Tc2_System > POUs > TIME
click on the function block
FB_PcWatchdog_BAPI
.
ð
The description of the function block can then be found under the
Documentation
tab or in the library
description under: FB_PcWatchDog_BAPI. If necessary, you can install the
Tc2_System
library at a
later stage via the
Add Library
button in the Library Manager.