Configuration
CX20x3
50
Version: 1.0
5. Select the appropriate LAN connection according to your cabling at the Embedded PC.
6. Confirm the settings with
OK
.
ð
You have successfully configured cable redundancy. Under the
Online
tab the EtherCAT slaves are
displayed, for which cable redundancy was configured.
Under
State
the state of the individual EtherCAT slaves is displayed. If, for example, the cable
connection between the EK1100 and EK1110 Bus Couplers is interrupted, the status of the Bus Coupler
changes. The message "LINK_MIS B" and "LINK_MIS A" appears under status.
Although the connection between the Bus Couplers is interrupted, the EtherCAT Terminals connected to
the EK1100 Bus Coupler show no fault.
If the cable connection is interrupted without cable redundancy at the same location, the terminals show
a fault under status.