Commissioning
"CX1190 UPS" tab:
Enable Automatic Shut Down:
If this switch is selected, then TwinCAT is stopped after an adjustable retention time, and "Windows XPe" is
shut down. Device 1 (here the CX1100) is switched off after the retention time has elapsed. Even when the
power fails for very short periods (<<10s) the system shuts down and the CX is switched off.
Problem:
If the voltage returns after TwinCAT has stopped but while "Windows XPe" is still in the process of
shutting down, the CX remains on, but "Windows XPe" remains stopped.
The UPS is fully charged again. The voltage must remain switched off for long enough for the UPS to switch
off, and only after this will reboot take place.
Configuration 2:
"Enable Automatic Shutdown"
and
"No Abort" are active:
CX1100-09xx
28
Version: 1.4