![Beckhoff CX1020 Series Скачать руководство пользователя страница 42](http://html1.mh-extra.com/html/beckhoff/cx1020-series/cx1020-series_hardware-documentation_2719440042.webp)
Product overview
40
Embedded PC
CX1020-N031/41 connections
The CX1020-N031 system interface features two RS422 / RS 485 interfaces, COM1 and COM2 (9 pin Sub-D plug
connector). If there is need for more than two serial interfaces two further RS422 / RS485 interfaces, COM3 and
COM4 (9 pin Sub-D plug connector) can be added to the system via the system interface CX1020-N41. The
maximum baud rate on all channels is 115 kBit. The pin assignment for all interfaces is equal and described below.
The interface parameter can be set in the operating system or in the PLC program.
RS232 COM interface (connector):
Pin assignment COM interface:
PIN
Signal
Type
Description
2
TxD+
Data-Out +
Transmit 422
3
RxD+
Data-In +
Receive 422
5 GND
Ground
Ground
6 VCC
VCC
+5V
7
TxD-
Data-Out -
Transmit 422
8
RxD-
Data-In -
Receive 422
For RS 485 Pin 2 and 3 ( Data +) as well as Pin7 and 8 (Data -) have to be connected..
Setting the interface parameter
If the system interface CX1020-N031/N041 resides at the end of the CX1020-system block, it is easy to access the
dip switches. The dip switches for the configuration of the RS485/422 interfaces can be found at the left side of the
module. If you remove the grey cover you can see the switch:
Содержание CX1020 Series
Страница 2: ......
Страница 5: ...Table of contents Embedded PC 3 Certifications 118 Support and service 119...
Страница 16: ...Product overview 14 Embedded PC Note For operating this unit need a power supply of type CX1100 001x...
Страница 62: ...Assembly and connecting 60 Embedded PC CX1000 N00x CX1020 N0x0 System interfaces...
Страница 65: ...Assembly and connecting Embedded PC 63 CX1100 09x0 UPS modules CX1100 0900 CX1100 0910...
Страница 66: ...Assembly and connecting 64 Embedded PC CX1100 0920...
Страница 68: ...Assembly and connecting 66 Embedded PC CX1500 Mxxx...