Product Description
2.2.3 DVI Input (X20)
X20
Connector DVI-D 3x8pole Digital LP-mount.
The CP-Link 4 transmitter box CU8803-0000 is connected with the Industrial PC via the DVI input (
X20
).
The maximum cable length is 1 m.
Pin
Signal
Pin
Signal
1
TMDS Data 2-
13
n.c.
2
TMDS Data 2+
14
+ 5 V Power Supply
3
TMDS Data2/4 shield
15
GND ( +5 V, Analog H/V Sync)
4
n.c.
16
Hot Plug Detect
5
n.c.
17
TMDS Data 0 -
6
DDC Clock
18
TMDS Data 0 +
7
DDC Data
19
TMDS Data 0/5 shield
8
Analog Vertical Sync
20
n.c.
9
TMDS Data 1 -
21
n.c.
10
TMDS Data 1 +
22
TMDS Clock shield
11
TMDS Data1/3 shield
23
TMDS Clock +
12
n.c.
24
TMDS Clock -
2.2.4 CP-Link 4 Output (X30)
X30
BA 1x8pole RJ45 Invers shield 2XLWL Lp-mount. Molex Nr: 43860-0016 Modular Jack
The CP-Link 4 transmitter box CU8803-0000 is connected with the Control Panel via the
CP-Link 4 output (
X30
).
Pin
Signal
Pin
Signal
1 CP-Link4_0P
5 CP-Link4_2N
2 CP-Link4_0N
6 CP-Link4_1N
3 CP-Link4_1P
7 CP-Link4_3P
4 CP-Link4_2P
8 CP-Link4_3N
CU8803-0000 disconnect power supply
Attention
If using the CP-Link 4 - One Cable Display Link, the 24 V power supply of the CP-Link 4
transmitter box must be switched off before disconnecting the CP-Link 4 output
connection.
CU8803-0000