Mounting and wiring
CPX27xx-0010
23
Version: 0.2
5.1.2
Mounting of the Panel PC
The Panel PC is installed in the cabinet wall with clamping levers. You need to cutout the cabinet wall for the
Panel PC. For the cutout dimensions of the Panel PC see chapter:
.
The Panel PC may only be mounted horizontally.
Requirements:
• Wall thickness of control cabinet is between 1 mm and 5 mm.
• 3.0 mm hexagon socket wrench.
Proceed as follows:
1. Release the clamping levers, turn the clamping levers to the side and take out the metal frame.
Clamping Lever
Metal frame
Rubber seal
2. Insert the Panel PC into the cutout and protect it from falling out.
3. Mount the metal frame on the back side of the cabinet wall to its previous position.
The metal frame is there to push the Panel PC evenly against the cabinet wall
Metal frame
Cabinet wall
4. Turn the clamping leavers to the side through 90°.
5. Retighten the screws. Tightening torque of the screw: 1 to 1.2 Nm.
ð
Check tensile strength of the clamping leaves and if the Panel PC is mounted correctly.