Basic information 

 

 

 

14 

BK7500 

 
 

The peripheral data in the process image  

 

 

When the bus coupler is first switched on it determines the configuration of 
the attached input/output terminals and automatically assigns the physical 
slots of the input/output channels to the addresses in the process image. 
 
The bus coupler sets up an internal list of assignments in which each of the 
input and  output channels has a specific position in the process image. A 
distinction is made here between input and output and between bit-oriented 
(digital) and byte-oriented (analog, or complex) signal processing.  
 
It also forms two  groups,  whereby  one contains only inputs  and the  other 
only  outputs.  In  each  group,  the  byte-oriented  channels  take  the  lowest 
addresses,  in  ascending  order,  and  these  are  then  followed  by  the  bit-
oriented channels. 
 

Digital signals 
(bit-oriented) 

Digital  signals  are  bit-oriented.  This  means  that  one  bit  of  the  process 
image is assigned to each digital channel. The bus coupler sets up a block 
of  memory  containing  the  current  input  bits  and  arranges  to  immediately 
write  out  the  bits  from  a  second  block  of  memory  which  belongs  to  the 
output channels. 
 
The  precise  assignment  of  the  input  and  output  channels  to  the  process 
image of the control unit is explained in detail in the Appendix by means of 
an example.  
 

Analog signals  
(byte-oriented) 

The processing of analog signals is always byte-oriented and analog input 
and output values are stored in memory in a two-byte representation. The 
values  are  held  as  "SIGNED  INTEGER”  or  "twos-complement”.  The  digit 
"0” represents the input/output value "0V”, "0mA” or "4mA”. When you use 
the  default settings, the maximum value of the input/output  value is  given 
by  "7FFF”  hex.  Negative  input/output  values,  such  as  -10V,  are 
represented  as  "8000”  hex  and  intermediate  values  are  correspondingly 
proportional  to  one  another.  The  full  range  of  15-bit  resolution  is  not 
realized  at  every  input/output  level.  If  you  have  an  actual  resolution  of  12 
bits, the remaining three bits have no effect on output and are read as "0” 
on  input.  Each  channel  also  possesses  a  control  and  status  byte  in  the 
lowest  value  byte.  If  the  control/status  byte  is  mapped  in  the  control  unit 
has  to  be  configured  in  the  master  configuration  software.  An  analog 
channel is represented by 2 bytes user data in the process image. 
 

Special 

signals 

and 

interface 

The BK7500 bus coupler supports bus terminals with additional interfaces, 
such  as  RS232,  RS485,  incremental  encoder,  etc..  These  signals  can  be 
regarded in the same way as the analog signals described above. A 16-bit 
data width may not be sufficient for all such special signals; the bus coupler 
can support any data width. With regard to accessing these values, please 
ensure  that  data  consistency  is  safeguarded.  That  is  to  say,  do  not  send 
any "update" command between access operations and do not switch the 
bus coupler to "freewheeling" mode. 

Default 

assignment 

of  

inputs  and  outputs  to  the 
process image 

When  the  bus  coupler  is  first  switched  on  it  determines  the  number  of 
attached  bus  terminals  and  sets  up  a  list  of  assignments.  This  list 
distinguishes  between  analog  channels  and  digital  channels  and  between 
input  and  output;  which  are  grouped  separately.  The  assignments  begin 
immediately to the left of the bus coupler. The software in the bus coupler 
creates  the  assignment  list  by  collecting  the  entries  for  the  individual 
channels  one  at  a  time,  counting  from  left  to  right.  These  assignments 
distinguish four groups: 
 
 

 

Содержание BK75 series

Страница 1: ...SERCOS Coupler Serial Real Time Communication System BK7500 Valid for all BK75xx Bus Coupler Technical Hardware Documentation Version 1 1 2006 10 30...

Страница 2: ...9 Mechanical construction and mounting 11 Electrical data 13 The peripheral data in the process image 14 Starting operation and diagnostics 17 Terminal bus error 18 Fieldbus error 18 Setting the Tran...

Страница 3: ...cked for consistency with performance data standards or other characteristics None of the statements of this manual represents a guarantee Garantie in the meaning of 443 BGB of the German Civil Code o...

Страница 4: ...ed and nullify the liability of Beckhoff Automation GmbH Description of safety symbols The following safety symbols are used in this documentation They are intended to alert the reader to the associat...

Страница 5: ...ventional terminal as the cabling level in the switch cabinet the switch cabinet can be made smaller The Beckhoff bus terminal system combines the advantages of a bus system with the functionality of...

Страница 6: ...couplers to attach the electronic terminal row quickly and easily to the various fieldbus systems and you can also subsequently convert to a different fieldbus system The bus coupler deals with all t...

Страница 7: ...ring terminals are connected in pairs to the power contacts The power supply to the power contacts has no connection to the power supply of the bus couplers The power input is designed to permit volta...

Страница 8: ...nd the bus terminals are effected by gold contacts at the right hand side of the bus coupler When the bus terminals are plugged together these gold contacts automatically complete the connection to th...

Страница 9: ...data telegrams are now also sent Each slave has its own station address The slave answers with a drive telegram AT and in this way indicates its readiness for changing the phase to communication phase...

Страница 10: ...e data for all the slave devices Because of different configurations the data length can vary Drive Telegram AT Each slave sends its output data in the appropriate time slot The telegram contains its...

Страница 11: ...us coupler and the various bus terminals onto a supporting 35mm C rail and a locking mechanism then prevents the individual housings from being removed You can remove them without effort if you first...

Страница 12: ...rminal interrupts the series of power contacts and constitutes the beginning of a new track The bus coupler can also be used to supply power to the power contacts The power contact labeled PE can be u...

Страница 13: ...00 Plug connection F SMA Norm IEC 872 2 Z1003 for Z1100 Baud rate 2 or 4 Mbaud 8 and 16 Mbaud in preparation Voltage of the power contact 24V DC AC Power contacts current drawn 10 A Electric strength...

Страница 14: ...ngs the maximum value of the input output value is given by 7FFF hex Negative input output values such as 10V are represented as 8000 hex and intermediate values are correspondingly proportional to on...

Страница 15: ...s RS232 SSI sensor interface Overview of the subdivision of the process image in the bus coupler Output data in the bus coupler O0 byte oriented data Ox Ox 1 bit oriented data Ox y Input data in the b...

Страница 16: ...adequate for processing digital signals but is not sufficient for transferring values longer than eight bits such as analog values The various bus systems guarantee consistency to the required length...

Страница 17: ...LED indicates the 24 V supply of the bus coupler The right hand LED signals the supply to the power contacts Local errors Two LEDs the I O LEDs in the area below the field bus status LEDs referred to...

Страница 18: ...ror No terminal connected attach terminals One of the terminals is defective halve the number of terminals attached and check whether the error is still present with the remaining terminals Repeat unt...

Страница 19: ...eld bus must access the bus coupler and the controller software must clear a cyclical trigger The green I O LED indicates access to the internal K bus and is reset after 100 ms The bus coupler queries...

Страница 20: ...rmation 20 BK7500 Setting the Station Address DIP switchh In the BK7500 the station address must be set at the coupler s DIP switch Example DIP Bit 1 8 2 0 0 1 0 2 2 3 0 4 0 5 2 6 2 7 201 1 0 0 8 0 0...

Страница 21: ...on from the slaves drive telegram and sends the output information to the slaves master data telegram A high data throughput is not in itself sufficient for successful use of a bus system Ease of hand...

Страница 22: ...0010 Current table Uint 16 read none Meaning This parameter allows a table to be selected in the Bus Coupler See also the section on the register structure It can also be selected in the MDT IDN Name...

Страница 23: ...e IDN Read Write IDN I O base 00000 Meaning This operating data contains the IDN of the first I O data channel i e the IDN of the channel container for this I O data channel The controller reads this...

Страница 24: ...KL5xxx strict compact 0x8007 16 bit data KL6xxx standard 0x8004 16 bit data KL6xxx alternative 0x8004 16 bit data IDN Name Type Attrib utes Default value Function S 2 0002 Channel IDN list IDN I O da...

Страница 25: ...efault value Function S 0 0185 Length of the data in the AT Read 0x Meaning Shows in the operating data the maximum length in bytes of the configurable data in the drive telegram IDN Name Type Attrib...

Страница 26: ...0 drive 1 0 I O station 0 1 mixed station Bit 0 1 1 1 reserved 0 device specified by the SERCOS working circle Bit 15 1 device specified by the manufacturer IDN Name Type Attrib utes Default value Fu...

Страница 27: ...plastic optical fibre with PU cladding Number of stations 254 stations in the ring with plastic optical fibre 0 3 m to 45 m Min bending radius 3 cm Transmission rate 2 4 8 Mbit s or 16 Mbit s Plug co...

Страница 28: ...must be checked Connect the BK7500 SERCOS Coupler to the SERCOS Master with the optical fibre The master s sender must be connected to the receiver at the BK7500 and the sender at the coupler must be...

Страница 29: ...n 1 Status Terminal Kl3062 UINT 16 S 2 0010 Chn 2 Data Terminal KL3062 UINT 16 S 2 0015 Chn 2 Status Terminal Kl3062 UINT 16 S 2 0040 Chn 1 16 Data All digital Input UINT 16 Configuration of the MDT S...

Страница 30: ...Compact Mode 0 1 UINT 16 0x0000 strict each clamp channel gets its own I O channel S 0 0291 I O Base UINT 16 0x1000 Pointer on the IDN S 1 0000 S 1 0000 Database UINT 16 0x2000 Pointer to the first I...

Страница 31: ...14 Diagnostic LEDs 15 DIP switch 18 End terminal 3 Example 26 Fiber optic conductor 25 Interfaces 5 K bus 3 11 Plugs 25 Power contacts 5 Power supply 5 Starting operation 15 If you have suggestions t...

Страница 32: ...here Beckhoff Headquarters Beckhoff Automation GmbH Eiserstr 5 33415 Verl Germany phone 49 0 5246 963 0 fax 49 0 5246 963 198 e mail info beckhoff com web www beckhoff com Beckhoff Support Support off...

Отзывы: