Parameterization and commissioning
BK11x0, BK1250
47
Version: 4.1
Once of these local clocks is the reference clock, based on which all other clocks are synchronized. See also
explanatory notes in the
. The reference clock must be the first DC-capable
EtherCAT slave. By default TwinCAT therefore selects the first DC-capable device as reference clock. This is
shown (and can be modified by the user) under advanced properties of the EtherCAT master. The standard
setting should not be changed, except in cases where external synchronization is recommended in the
relevant documentation, for example.
Fig. 33:
Advanced Distributed Clocks settings in the EtherCAT master
The figure shows how TwinCAT selects the EL1252 as reference clock by default, since the preceding
components do not support DC.
Settings EtherCAT device
System and infrastructure devices such as EK1100 or EK1122 couplers and junction etc. do not require
Distributed Clocks to function properly. Nevertheless, it may be topologically expedient to designate the first
coupler in an EtherCAT system as reference clock, for example. For this reason, from a certain level the
infrastructure components are able to operate as reference clocks, based on special configuration settings.
According to the following table (
DC support from rev/firmware version
), the components support activation
of distributed clocks:
Device
XML revision in the configura-
tion
Serial number of the component
BK1150
from BK1150-0000-0016
from firmware 01: xxxx01yy
CU1128
from CU1128-0000-0000
from firmware 00: xxxx00yy
EK1100
from EK1100-0000-0017
from firmware 06: xxxx06yy
EK1101
from EK1101-0000-0017
from firmware 01: xxxx01yy
EK1501
from EK1501-0000-0017
from firmware 01: xxxx01yy
EK1501-0010
from EK1501-0010-0017
from firmware 02: xxxx02yy
EK1122
from EK1122-0000-0017
from firmware 01: xxxx02yy
EK1521
from EK1521-0000-0018
from firmware 03: xxxx03yy
EK1541
from EK1541-0000-0016
from firmware 01: xxxx01yy
EK1561
from EK1561-0000-0016
from firmware 01: xxxx01yy
EK1521-0010
from EK1521-0010-0018
from firmware 03: xxxx03yy
EK1814
from EK1814-0000-0016
from firmware 00: xxxx00yy
To ensure that TwinCAT uses such a component as DC reference clock, a manual intervention during the
configuration setup is required, as shown here using the EK1100 as an example.
The checkboxes “
Cyclic Mode Enable”
and “
Use as potential Reference Clock”
must be set.