Priming The Pump

Initiate a call for heat.
When the burner starts, press and hold the reset button for 15 
seconds until the yellow light turns on.
Release the button.  The yellow light will turn off and the burner 
will start again.
At burner start up, click the reset button while the igniter is still on 
to enter Pump Prime mode.  The yellow light will turn on.
Bleed the pump until all froth and bubbles are purged. 
If necessary, repeat steps 4 and 5 until the pump is fully primed 
and the oil is free of bubbles.
When 

fi

 nished, hold the reset button or remove the call for heat to 

exit Pump Prime mode and return to Standby.

1.
2.

3.

4.

5.
6.

7.

Operation

Sequence of Operation

Yellow LED Flashes

Cad Cell Resistance

1

Normal (0 - 400 ohms)

2

Normal (400 - 800 ohms)

3

Normal (800 - 1600 ohms)

4

Limited (1600 ohms - Lockout)

Resetting From Restricted Lockout

If the control locks out three times without a satis

fi

 ed call for 

heat or fails the motor relay check, the Lockout becomes 
restricted in order to prevent repetitious resetting by the 
homeowner.  To reset, hold the button down for 15 seconds 
until the red light turns off and the yellow LED turns on.

Disable Function

Any time the burner is running, press and hold the reset 
button to disable the burner.  The burner will remain off as 
long as the button is held.

Cad Cell Resistance Indicator

During the burner Run state, click  the reset button to check 
the cad cell 

fl

 ame resistance range.  The yellow light will 

fl

 ash 

1 to 4 times depending on the amount of light detected by the 
cad cell.  See the table below:

Cross-Reference Chart

Beckett GeniSys

Control Part No.

Lockout

Time

Valve-on

delay time

2

Motor-off

delay time

2

Replaces

Honeywell:

Replaces

Carlin:

7505A 0000

15 sec

-

-

R7184A, R8184G

48245, 40200 42230, 50200

1

7505B 1500

15 sec

15 sec

-

R7184B

-

7505P 1515

15 sec

15 sec

15 sec

R7184P, R7184U

1

60200

1

7505P 1530

15 sec

15 sec

30 sec

R7184P, R7184U

1

60200

1

7505P 152M

15 sec

15 sec

2 min

R7184P, R7184U

1

60200

1

1) Beckett snap-in alarm module required for direct replacement of the control.   2) Valve-on delay and motor-off delay timings on all models are programmable with Beckett snap-in programming display.  Other factory set 
timings are available.  Contact Beckett for alternate timings.

Electrical Ratings

Inputs

Voltage: 102 to 132 Vac
Current: 150 mA plus burner motor, igniter, and valve loads
Frequency: 60 Hz

Outputs

Motor: 120 Vac, 10 full load amps (FLA*), 60 locked rotor amps (LRA)

Note

 – Reduce motor FLA rating by igniter current

Igniter: 120 Vac, 3 A @ 0.7 PF min
Solenoid Valve: 120 Vac, 1 A @ 0.7 PF min
Thermostat Anticipator Current: 0.1 A (If applicable)
Thermostat Voltage: 24 Vac (If applicable)

Application Ratings

Oil Burner Input: < 20gph
Control Programming: UL372 Group 2 

Environmental Ratings

Storage & Operating Ambient Temp.: -40°F to +150°F (-40°C to 
+65°C)
Moisture: 5 to 95% RH, non-condensing and non-crystallizing

Approvals

Underwriters Laboratory Recognition per UL372 and UL1998, 
and CSA C22.2 No. 199

Standby

Motor-off 

delay

Valve-on 

delay

Trial for
ignition

Ignition 

carryover

Run

Lockout

Recycle

Pump
prime

1

2

3

4

9

7

6

5

8