background image

Section: BURNER START-UP

24

Burner Start-up

Explosion, Fire, and 

Asphyxiation Hazard

Professional Installation & Service 

Required.  Incorrect installation an

d set up 

c

ould lead to equipment malfunction.

Asphyxiation Hazard

It is recommended that you measure the oxygen 

(O

2

) early in the test sequence because high levels 

of carbon monoxide (CO) can be created at very 

low or very high O

2

 levels.  The typical operating 

range is between 3%-5% O

2

.

This burner must be installed and prepared for start-up by a 

qualified service technician who is trained and experienced 

in gas burner system installation and operation.

Do not attempt to start the burner unless you are 

fully qualified.

Do not continue with this procedure without the proper 

test instruments.

Carefully follow the wiring diagrams, control instruction 

sheets, control sequence of operation, test procedures 

and all appliance manufacturer’s directions that pertain 

to this installation.

Test Instruments

The following calibrated test equipment is required to 

properly install the appliance.  They should be calibrated 

and in good working order.

 

|

A combustion analyzer capable of measuring 

oxygen (or carbon dioxide), carbon monoxide, 

stack temperature, ambient temperature, and 

appliance efficiency.

 

|

Electrical multi-meter capable of measuring voltage, 

ohms, amps, and DC micro-amps for measuring the 

flame signal.

 

|

Calibrated manometers and pressure gauges 

capable of measuring all pressure ranges in the gas 

supply and appliance draft.  This could typically range 

from a few PSI to 0.1” W.C.

Burner Start Procedure 

(Before proceeding, turn off and lock out electrical 
power and close the main shut off cock to shut off 
gas to the burner.)

1.  With the power and main gas supply to the burner 

turned off, make sure gas has not accumulated in the 

boiler or flues. 

2.  Check the initial air settings (shutter & band) for input 

firing rate.  See 

Table 8

 on page 25 for initial air 

settings. 

3.  With the main shutoff cock closed. Set the limit or 

controller to call for heat then apply power to start the 

burner. 

4. 

Verify Burner Safety Control Function

 – In order 

to check the function of each component (i.e.: 7590 

sequence, airflow proving switch, ignition transformer, 

gas valves, safety lockout timing, etc.), with the main 

shutoff cock closed, monitor a complete burner run 

sequence.  Note that the 7590C control will enter a 

5 minute waiting time after failing the trial for ignition 

since the fuel supply has been closed off.  Reset the 

control by pressing and holding the reset button while 

the control is powered.

5. 

Verify Flame Sensor Function

 – If 7590 operation 

sequence and function is correct, turn off power and 

remove sensor wire from bottom of 7590 control.  

Turn on power and fuel and initiate Call for Heat.  

Verify that burner fires up and the gas valve closes.  

After control locks out, flame shall go off. 

6.  Turn power off and reattach sensor wire.  Turn power 

back on and reset the control using reset button.  

Initiate Call for Heat.

7.  After you have observed main flame for a brief time, 

press the reset button on the control for 1 second to 

shut down and re-start the burner.  Monitor the flame 

and safety shutoff valves to assure that shutdown 

is controlled by the valves and that they operate 

properly.  With this test passed, you may safely initiate 

automatic start-ups on subsequent cycles.

8.  While the burner is firing, examine the vent system 

for evidence of leaks, obstructions, and for correct 

function of the barometric draft control.  Leak test all 

gas piping from the burner to the utility supply piping.  

If leaks are found, correct them immediately.

9. 

Low gas pressure switch

 – With the burner firing 

and a manometer attached to a test port near the low 

pressure switch, gradually close the main leak test 

cock to shut off the gas supply. Note the pressure at 

which the low gas pressure switch opens and shuts 

the burner off. Manually reset the switch. The low gas 

pressure switch should be set at half of the normal 

supply pressure in the line.

10. 

High gas pressure switch

 – With the burner firing 

and a manometer attached to the test port nearest 

the high pressure switch, gradually increase the gas 

pressure until the high pressure switch opens and 

shuts the burner off. Note the pressure and manually 

reset the switch. The high gas pressure switch should 

be set at one and one half times the high fire manifold 

pressure (see nameplate data in 

Figure 1

 or set 

switch as determined by testing).

Содержание CG10-24

Страница 1: ...her flammable vapors and liquids in the vicinity of this or any other appliance WHATTO DO IFYOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in y...

Страница 2: ...Applications 6 Figure 4 Burner Configuration for 600 to 1200 MBH Applications 7 Figure 5 Gas Gun Assembly Component Familiarization 8 Figure 6 Vent Pipe with Draft Regulator 9 Figure 7 Chimney Design...

Страница 3: ...Keep this manual for your records and provide it to your qualified service agency for use in professionally setting up and maintaining your burner Your CG10 burner will provide years of efficient ope...

Страница 4: ...ic Direct Spark Motor Thermally Protected Manual Reset Combustion Air Proving Differential Pressure Switch Weight 40 lbs Mounting Orientation Up to 90 from upright with motor shaft horizontal Dimensio...

Страница 5: ...welded depending on application Figure 1 Burner Dimensions General Model Information Serial Number Including Date Code Rating Information Approval Agency Symbols R W Beckett Construction Setting Data...

Страница 6: ...t high rates Two air tube shrouds shape and stabilize the base of the flame Two burner head styles are available for each firing range to provide mixing control and retain the flame See Table 3 and Ta...

Страница 7: ...lower wheel Air Guide Chassis Firing Rate MBH Burner Head Blower Wheel Air Inlet Scroll Extension CG10B 601 756 10 4 6 31 dia x 2 42 w Part No 21339 Air Guide Part No 178 Installed 10 4S 757 952 10 5...

Страница 8: ...wires in location shown below see warning Electrical Shock and Explosion Hazard Failure to secure wires away from contact with the blower wheel could result in electrical shock or explosion hazard Ign...

Страница 9: ...t project into the chimney see Figure 6 Explosion Fire and Asphyxiation Hazard Wet or dusty environments could lead to blocked air passages corrosion damage to components impaired combustion performan...

Страница 10: ...inimum Clearence 2 FT NOTE Correct chimney design is shown by dotted lines Incorrect chimney design as shown by the solid lines may result in down drafts Figure 7 Chimney Design Above the Roof 5 Any l...

Страница 11: ...each opening in the enclosure should be 350 sq in 350 000 1 000 x 1 sq in 350 sq in A 350 sq in opening would typically be 12 x30 or 19 x19 Buildings with LessThan Adequate Air Infiltration If the bur...

Страница 12: ...and tables for pipe sizing as outlined in ANSI Z223 1 NFPA 54 All gas piping installation must comply with the latest edition of the National Fuel Gas Code ANSI Z223 1 NFPA 54 and other applicable loc...

Страница 13: ...5 590 800 1650 2700 4700 9700 40 130 245 500 760 1450 2300 4100 8300 50 115 215 440 670 1270 2000 3600 7400 60 105 195 400 610 1150 1850 3250 6800 70 96 180 370 560 1050 1700 3000 6200 80 90 170 350 5...

Страница 14: ...asket Verify that all boiler sections canopy and access plates or doors are fully equipped with gaskets and sealed against any leakage Mount the Burner The burner specified for packaged equipment will...

Страница 15: ...ve component that requires atmospheric air pressure to balance a diaphragm Vent lines must be run to the outdoors with the termination point away from fresh air intakes and windows The terminal openin...

Страница 16: ...al nipples Key Figure 10 thru Figure 12 Abbrev Item Description CGV HGPS LGPS MSC MLTC PRSSOV PRV SSOV1 SSOV2 TC TP U Combination Gas Valve High Gas Pressure Switch Low Gas Pressure Switch Main Shutof...

Страница 17: ...Major Components Explosion Fire and Asphyxiation Hazard This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer s instructions and all applicable codes...

Страница 18: ...418 3226409U CG10 3S CG10 6S 3246705U 0 510 3226409U CG10 4S 3246706U 0 459 3226409U CG10 5S 3246707U 0 482 3226409U CG10 4 3246723U 0 547 3226409U CG10 5 3246724U 0 578 3226409U CG10 6 3246725U 0 59...

Страница 19: ...red in accordance with manufacturer s instructions Wire the burner in compliance with all instructions and diagrams provided by the appliance manufacturer Verify operation of all controls in accordanc...

Страница 20: ...A good ground is required to maintain a good flame sensing Use a ground fault interrupt if grounding of the burner can be compromised Explosion Fire and Asphyxiation Hazard Do not tamper with or bypas...

Страница 21: ...SURE Notes L1 power shall be run through the limits for high gas low gas LWCO high limit and operating control Solid lines factor wiring Dashed lines field wiring CONFIDENTIAL DRAWING PROPERTY OF R W...

Страница 22: ...AGRAM 7590WD02 DLW 09 01 15 7590 CONTROL RC 09 01 15 C NOT TO SCALE 1 OF 1 L1 L2 MOTOR L2 MTR IGNITER L2 IGN FLAME ROD WHITE ORANGE WHITE 7590 CONTROL TERMINAL TERMINAL COLOR IGNITER MOTOR BLUE W WHIT...

Страница 23: ...ATUS Status LED ON Pre purge FLAME MV STATUS Status LED Flashes Ignition FLAME MV STATUS Status MV LEDs On Run FLAME MV STATUS Status MV Flame LEDs On End Call for Heat FLAME MV STATUS LEDs Off Timers...

Страница 24: ...ach component i e 7590 sequence airflow proving switch ignition transformer gas valves safety lockout timing etc with the main shutoff cock closed monitor a complete burner run sequence Note that the...

Страница 25: ...10 1 3 6 1 8 10 1 4 1 2 1 10 3 900 CG10 5S 4 0 2 0 10 3 4 2 2 1 10 4 4 5 2 2 10 4 5 0 2 5 10 6 1000 CG10 6S 3 2 1 6 10 0 3 4 1 7 10 2 3 7 1 8 10 3 4 2 2 1 10 6 1100 CG10 6S 3 9 1 9 10 2 4 1 2 1 10 4...

Страница 26: ...6S CG10 5S CG10 4S CG10 3S CG10 2S CG10 1S 0 200 400 600 800 1000 1200 1400 0 1 2 3 4 5 Rate MBH Pressure Drop In WC CG10 6 CG10 5 CG10 4 CG10 3 CG10 2 CG10 1 Figure 19 Manifold to Furnace Pressure Dr...

Страница 27: ...urner 11 Check for leaks at the gas valve outlet pressure tap plug using a leak detection solution or soapsuds Bubbles forming indicate a leak SHUT OFF GAS AND FIX ALL LEAKS IMMEDIATELY If the burner...

Страница 28: ...function is correct turn off power and remove sensor wire from bottom of 7590 control Turn on power and fuel and initiate Call for Heat Verify that burner fires up and the gas valve closes After cont...

Страница 29: ...ion performance readings burner settings and appliance data on the start up form in the back of this manual If the burner is firing LP gas you must also record set up information on the propane conver...

Страница 30: ...t paying special attention to the air diffuser 8 Inspect the flame rod for oxidation or distortion Clean all surfaces set the probe position and insure that the flame rod is securely fastened Refer to...

Страница 31: ...nitor several burner start up cycles Verify prompt ignition and flame stability 4 Calculate the input firing rate and compare to the appliance specifications 5 Monitor the stack temperature Compare to...

Страница 32: ...fy burner model on adjustment scale Verify O ring is in place and lubricated Figure 23 Gas Gun Assembly Top View CG10 1S 10 6S CG10 3 10 6 CG10 1 10 2 END BELL MOTOR END BELL MOTOR 0 020 0 020 0 030 t...

Страница 33: ...5U 11 Air Band 5151503 12 24V Transformer 52310002U 13 Air Inlet Air Guide 300 600 MBH 189U Air Guide 600 1 000 MBH 178U Inlet Sleeve 32336U Item Description Beckett Part No 14 Blower Wheel CG10 300 6...

Страница 34: ...0 4 104U 10 4S 104SU 10 5 105U 10 5S 105SU 10 6 106U 10 6S 106SU 2 Spring Clamps 4 pack 3236501U 3 Electrode Set with Cable 10 4 10 6 22225U 10 1 10 3 2191201U 10 1S 10 6S 2191205U 4 Flame Rod with Ca...

Страница 35: ...eration Verified Temperature YES NO Pressure YES NO LWCO YES NO Other Limits YES NO n a Burner Fuel Natural Gas Propane Model ________________ Serial _________________________ Combustion Head ________...

Страница 36: ...copy of warranty form 61545 please choose one of the following options 1 Visit our website at www beckettcorp com warranty 2 Email your request to rwb customer service beckettcorp com 3 Write to R W...

Отзывы: