Beckett CF1000 Скачать руководство пользователя страница 7

Form 6104 BCF10-R06

7

The fuel unit nozzle port pressure is factory set at 300 psig. 
Some original equipment manufacturer burner applications 
may call for a lower pressure to obtain a required fi ring 
rate.  Do not change this pressure unless directed to do so 
by the appliance manufacturer.

Vent system

The fl ue gas venting system must be in good condition and 
must comply with all applicable codes.

Electrical supply

Verify that the power connections available are correct for 
the burner. All power must be supplied through fused dis-
connect switches.

Verify burner components —

Burner box

, Model CF1000

Air tube assembly

 

Mounting fl ange kit

Pedestal mounting assembly kit

 (recommended)

Oil nozzle

, per 

Table 1

 — Only 45° to 70° solid pattern 

nozzles are recommended unless otherwise specifi ed  by 
appliance manufacturer. (See specifi c  appliance  recom-
mendation sheet or refer to OEM Spec Guide).  Find the 
required fi ring rate in the 300 psig column (factory-set fuel 
unit pressure). Select the corresponding nozzle from col-
umn 1 (

Rated gph @ 100 psig

).

Verify fi ring rate

Refer to appliance manufacturer’s instructions (if available) 
for fi ring rate and nozzle selection. Otherwise, the maximum 
recommended  fi ring rate for the burner depends on the 
length of the fi ring chamber and the distance from the 
burner center to the chamber fl oor. Verify that the chamber 
dimensions are at least as large as the minimum values 
given in 

Figure 1

. If the appliance dimensions are smaller 

than recommended, reduce the fi ring rate accordingly.

Verify air tube

The information in this section may be disregarded if the 
air tube is supplied by the appliance manufacturer.

Two tube arrangements are available –

 Tube 

A

 — 4.0 to 10.0 GPH per 

Table 2

 Tube 

B

 — 7.0 to 10.0 GPH per 

Table 2

Maximum fi ring capacity depends on the fi rebox pressure. 
Use 

Table 2

 to verify the correct air tube type for the fi ring 

rate required. Use Tube 

B

 only when Tube 

A

 cannot pro-

vide the fi ring rate required.

See 

Figure 2

 to verify the correct air tube length and air 

tube combination code.

y

‰
y

‰

y

‰
y
y
y
y
y

‰

y

‰

y

y

y

y

Firing Rate

Minimum Dimensions

(refractory-lined)

(wet-base boilers)

A

L

A

L

0 to 5 gph

7.0”

25.0”

7.0”

25.0”

5 to 10 gph

8.0”

35.0”

8.0”

40.0”

 

Install the burner with a 2 deg. pitch as shown

E  

Insertion depth

G  

Air tube to inside of chamber

      0.25” +/- 0.125

T  

Air tube length

D  

Tube diameter

Figure 2 - Air Tube Mounting Dimensions

Figure 1. Min. Combustion Chamber Dimensions

Air Tube Length           

 

(Dimension 

T

)

A.T.C. Codes

(A.T.C. = Air Tube Combination)

Tube A

(Dim. 

D

 = 5-1/2”)

Tube B

(Dim. 

D

 = 5-3/4”)

0

6.75”

CF66KD

CF66KE

10.25”

CF102KD

CF102KE

13.75”

CF136KD

CF136KE

17.75”

CF176KD

CF176KE

Содержание CF1000

Страница 1: ...tart up or service work Save this manual for future reference y y y Incorrect installation adjustment or misuse of this burner could result in death severe personal injury or substantial property dama...

Страница 2: ...2 Form 6104 BCF10 R06...

Страница 3: ...bustion air supply 6 Clearances 6 Fuel supply 6 Nozzle pressure 6 Vent system 7 Electrical supply 7 Verify burner components 7 Verify firing input range 7 Verify air tube 7 Mount the burner 8 10 Mount...

Страница 4: ...an If at any time the burner does not appear to be operating properly immediately contact your qualified service agency for consultation We recommend annual inspection service of your oil heating syst...

Страница 5: ...asphyxiation explosion or fire Follow These Instructions Exactly 50 Hz motors The burner ratings air settings and nozzle ratings are based on standard 60 hz motors at 3450 rpm Derate all ratings 20 wh...

Страница 6: ...r is equipped with an H fuel unit The return line provided by the two pipe system is needed to purge the air from the fuel lines and minimize the likelihood of air related problems during operation y...

Страница 7: ...e burner depends on the length of the firing chamber and the distance from the burner center to the chamber floor Verify that the chamber dimensions are at least as large as the minimum values given i...

Страница 8: ...unt flange s on air tube Mount air tube to burner Remove the rear access door from the back of the burner for improved access to the interior Attach the air tube to the burner with the bolts and acorn...

Страница 9: ...acorn nut d Top acorn nut for setting dim Z only e Indicator adjusting plate f Secondary adjusting plate g Primary adjusting plate Figure 4 Nozzle and nozzle line assembly Measure dimension Z from fro...

Страница 10: ...item c Secure the burner to the appliance by tightening the nuts on the burner flange mounting studs Then secure the pedestal support floor flange set screw to the pipe y y y Oil supply return lines I...

Страница 11: ...t comply with the latest edition of NFPA 31 Canada CSA B139 and all applicable codes Do not install valves in return line If the oil supply inlet pressure to the pump exceeds 3 psig or for gravity fee...

Страница 12: ...ation If any of these items are not clear or are unavailable call Beckett at 1 800 645 2876 for assistance y y y y y Incorrect installation and mishandling of start up could lead to equipment malfunct...

Страница 13: ...ing dimension Z only do not loosen after setting dimension Z e Indicator adjusting plate f Secondary adjusting plate g Primary adjusting plate h Copper oil line from oil valve to nozzle line Sequence...

Страница 14: ...ialsettingshouldbeadequateforstartingtheburner Tighten the screw to secure the adjusting plate Once the burner is in operation the air setting will be adjusted for best performance as discussed later...

Страница 15: ...contact the Fire De partment Carefully follow their directions Keep a fire extinguisher nearby and ready for use y y y y y y Failure to follow these instructions could lead to equipment malfunction an...

Страница 16: ...y y y Set air adjusting plate Figure 12 Allow the burner to run until the appliance has warmed sufficiently Visually check the flame The flame should not be dark orange or smoky If the flame appears...

Страница 17: ...ectrodes if tips are rounded Inspect the igniter spring contacts Clean the cad cell lens surface if necessary Inspect all gaskets Replace any that are damaged or would fail to seal adequately Inspect...

Страница 18: ...Plug Coupling Access Door Use with threaded hole Use with rectangular opening 32439U 16703GY 14 Head assembly CF1000 combustion 51203P 15 Electrode assembly All models 51212 16 Ignition leads 8 1 4 l...

Страница 19: ...Form 6104 BCF10 R06 19 Figure 14 Adjustable mount ing plates for CF1000 1 2 3 4 5 6 8 7 13 16 15 14 17 18 19 20 21 22 10 9 11 12 Figure 13 Adjustable Mount ing Plates for CF1000...

Страница 20: ...E PROTECTION ASSOCIATION THE LATEST EDITION OF THE NATIONAL FUEL GAS CODE NFPA NO 54 AND IN ACCORDANCE WITH ALL APPLICABLE LOCAL STATE AND NATIONAL CODES HAVING JURISDICTIONAL AUTHORITY Equipment whic...

Отзывы: