What to do if Low Water Lockout 

Occurs with New Sensor

1.  Turn off power to the control. 
2.  Remove sensor from well and disconnect green 

sensor wire.  

Leave the main sensor cable 

connected to the control.

3.  Being careful not to allow the sensor or the green 

wire to touch anywhere in the terminal area of the 

control, restore power to the control.  Within 30 

seconds the AquaSmart control should enter into 

Lockout Water Low. 

LOCKOUT

WATER LOW

4.  Use the 1,000 Ohm resistor attached to this 

instruction sheet.  Place one resistor lead on the 

metal pin of the sensor, the second resistor lead 

should be on a metal portion of the connector for 

the green wire coming from the sensor (see pictures 

below).  Hold the resistor in place with fingers.   

Within 30 seconds the Lockout Low Water fault on 

the display should clear.  

If the Lockout Low Water 

clears, the sensor is operating properly. 

Other Possible Causes:

• 

Poor connections in the LWCO circuit wiring

• 

Deposit build up on the well or boiler vessel 

• 

Conductivity issues with the water.

5.  Recheck the continuity of the LWCO circuit following 

the procedure on the previous page.  

6.  If the sensor is good and the LWCO connection 

wiring is good, drain water from the boiler, remove 

the well and check for deposit build up on the well.   

Clean if necessary and reinstall the well.  Refill the 

boiler.  Check for proper operation of the LWCO  

circuit.

7.  If the sensor, LWCO connection wiring and well are 

good, attempting to measure the resistance through 

the water may provide some indication of the 

conductivity of the water in the system.  Remove the 

sensor from the well.  Place one of the ohm meter 

probes on the metal tube inside the well and place 

the second probe on the metal of the boiler vessel.

• 

100K ohms or above - water not in contact with 

well, deposit build up in boiler vessel

• 

5K-100K ohms - intermittent operation could 

occur

• 

5K ohms or below - LWCO should operate

These are rough guidelines only.

    