Preparatory measures

All tasks for transport, installation and commissioning as well as for servicing should be carried 
out by

 qualified technicians (IEC 364 or CENELEC HD 384 or DIN VDE 0100 and IEC 664 

or DIN VDE 0110 and national accident prevention regulations) .

Qualified technicians are persons that are familiar with the setting up, assembly, commis

-

sioning and operation of the product and have the appropriate qualifications for their tasks.

Setting up

The setting up and the cooling of the devices need to be done according to the directives of 
the corresponding pump documentation.

The frequency converters need to be protected against excessive strain. In particular, compo-
nents must neither be bent nor insulation dimensions changed during transport and handling. 
Avoid touching electronic components and contacts.

Frequency converters contain electrostatically-endangered components that can be easily 
damaged by improper handling. Electrical components must neither be damaged mechanically 
nor destroyed (possible health hazard!). 

Electrical connection

Frequency converters are components for use in industrial high-voltage systems and are 
operated with voltages that can cause serious injuries or even death if touched. 

Installations and maintenance may only be done by 

qualified electricians

 and when the 

device is free of voltage. The operating instructions have to be available for these persons 
at all times and be dutifully observed by them.

On the circuit boards there are highly sensitive MOS semiconductor devices that are es-
pecially sensitive to static electricity. Therefore, please avoid touching the circuit boards or 
components with your hands or with metallic objects. Only the screws of the terminal strips 
may be touched by insulated screwdrivers when wires are connected.

The frequency converter is intended for permanent connection only and may not be operated 
without an effective earth connection that complies with the local regulations for high leakage 
currents

(> 3.5 mA). VDE 0160 prescribes the laying of a second earth line or an earth cross-section 
of at least 10 mm

2

.

If personal or fire protection is required when using the FC, all-current sensitive residual-

current devices (type B RCD) must be used (in accordance with VDE 0664). They provide 
reliable protection for the high-frequency AC currents and the smooth and pulsating DC re-
sidual currents that occur during FC operation. Conventional type A residual-current devices 
are not suitable for this purpose. 

When working on frequency converters that are electrically charged, the relevant national 
accident prevention regulations must be observed.

The local regulations on installing electrical systems as well as the accident prevention re-
gulations must be observed. 

The electrical installation is to be carried out according to the applicable regulations (e.g. 
cable cross-sections, fuses, earth lines). 

Information on EMC-compliant installation – such as insulation, earthing, arrangement of filters 

and the laying of lines – can be found in the documentation for the frequency converters. 
Always observe these instructions also with CE-marked frequency converters. The responsi-
bility of complying with the limits required by the EMC regulations lies with the manufacturer 
of the system or machine.

Содержание VariAir VAU4/3

Страница 1: ...www becker international com 1 28100241101 11 12 operating instructions Frequency converter vAU4 3 QUICK START GUIDE ...

Страница 2: ...ns The latter should be read thoroughly before initial start up The quick start guide contains safety instructions and helps the user to put the basic model of the VAU 4 3 into operation and to operate it with the default settings Intended use i Frequency converters are components that are intended for installation into electrical systems or machines When being installed into machines the commissi...

Страница 3: ...r devices that are es pecially sensitive to static electricity Therefore please avoid touching the circuit boards or components with your hands or with metallic objects Only the screws of the terminal strips may be touched by insulated screwdrivers when wires are connected The frequency converter is intended for permanent connection only and may not be operated without an effective earth connectio...

Страница 4: ...y charged parts and line connections must not be touched directly after frequency converters are disconnected from the supply voltage as the capacitors may be charged Observe the corresponding signs about this on the frequency converters During operation all covers must be kept closed The frequency converter is maintenance free under normal operating conditions If the air is dusty the cooling surf...

Страница 5: ...Rel 2 Terminal Connection L1 L2 L3 Mains feeder phase L1 L2 L3 PE Mains feeder earth line PE U V W Connection strands motor winding U V W X Y Z Feeder phase external ventilator phase L1 L2 L3 optional Connection terminals of the bottom row of the double decker terminal block Terminal Connection 1 24 V SELV 1 24 V DC fixed voltage output 2 Digital 1 Digital input 1 Digital 2 Digital input 2 Digital...

Страница 6: ... switch block 1 with 4 switches Setting Function DIP switch 1 OFF Speed set operation ON Controlled operation DIP switch 2 OFF No control via RS485 field bus interface ON Control via RS485 field bus interface DIP switch 3 OFF No analogue control ON Analogue control DIP switch 4 OFF Pressure mode ON Vacuum mode DIP switch block 2 with 2 switches DIP switch 1 DIP switch 2 Analogue input 1 OFF OFF 0 ...

Страница 7: ...with the continuously lit red LED Table of possible error messages Display Malfunction Short circuit Overvoltage Intermediate circuit Undervoltage Intermediate circuit Overtemperature motor Mains interruption Offset current sensor Overtemperature Power output stage Overcurrent Inner temperature too high Charge relay defective I2 t limitation Earth fault Feldbus timeout IO controller defective RS48...

Страница 8: ...m installation altitude Up to 1000 m above sea level without loss of performance Weight kg 5 6 Type of protection IP 55 Maximum cross section power supply mm2 2 5 Maximum cross section pilot wires mm2 1 5 Maximum connection cross section external ventilator mm2 2 5 Terminal range power cable mm 7 0 13 width across flats 25 Terminal range pilot wires mm 4 5 9 0 width across flats 20 Certifications ...