background image

4

Operating Instructions

4906

 630

 0

14

 0

   

03/1

4

The running time is the length of time that the drive stays 

on.

If the "S" button is held down for longer than 3 seconds, 

 will appear on the display (Fig. 14, standard value 

1  minute  and  30  seconds).  The  running  time  can  now 

be changed using the 

 and 

  buttons.  After  the  run-

ning time has elapsed, electrical power is removed from 

the drive, and reversal is carried out if active. By press-

ing the "S" button repeatedly, you enter the "Set reversal 

time" mode. This is shown by a  , and the running time 

that has been set is saved at the same time. The value for 

the reversal time can be varied between "01" and "99"  

(Fig. 13).

Changing the factory-set running time/reversal time

Fig. 14

By pressing the " " button, the reversal time is switched 

off (

, Fig. 13). The maximum reversal time ("99" on 

the display) corresponds to about 3.2 seconds. Press the 

"S" button again to return to operating mode. If the rever-

sal time is active, then after the running time has elapsed, 

the drive is operated in the "UP" direction for the duration 

of the set reversal time. Depending on the setting and on 

the speed of the drive, the first slats of the roller shutter 

are then cleared again to provide ventilation, for example.

When the set running time has completely elapsed, the 

roller shutter can be closed completely by hand.

Technical data

What to do if...?

Problem

Cause

Remedy

The roller shutter moves downwards about 15 

minutes after it has been opened.

The set twilight value has been reached, or the 

sensor is covered.

Check the twilight value and the position of the 

sensor on the window. It may have become 

detached from the pane.

The U26 does not carry out the set switching 

commands, or does so after a delay.

The time is set to manual or holiday operation.

Put the time into "automatic mode".

The sun and twilight parameters that have been 

set cannot be changed, or are not displayed.

A sensor is not inserted, or else either the sen-

sor or its connecting cable is faulty.

Check the sensor, the sensor cable and the 

connecting plug.

Structural modifications and incorrect installation which are not in accordance with these and our other instructions can result in serious injuries, e.g., 

crushing of limbs. Therefore, structural modifications may only be carried out with our prior approval and strictly in accordance with our instructions, 

particularly the information contained in these Assembly and Operating Instructions.

Any further processing of the products which does not comply with their intended use is not permitted. 

The end product manufacturer and fitter have to ensure that all the relevant current statutory, official and, in particular, EMC regulations are adhered to 

during utilisation of our products, especially with regard to end product manufacture, installation and customer advice.

Warranty

Subject to technical changes without notice.

The controller can be integrated into switching units from many other manufacturers with central board dimensions of 55 x 55 mm.

Examples:

Manufacturer

Type

Berker

S1, B3, B7

Gira

Standard, E2, Event, Esprit

Jung

AS, A500, A-Creation, A-Creation-Glas, A-Plus

Merten

M-Smart, M-Arc, M-Plan, M-Plan-Glas, M1, Atelier, M-Star

 

Switching range

Supply voltage: 

230 V±10%, 50-60 Hz

Output: 

Phase connected via two relay contacts 

 

for UP and DOWN

Switched power: 

5A at cos 

ϕ

=1

Power reserve: 

approx. 5 hrs.

Display: LCD

Ambient temperature: 

0 to +55 °C

Mounting: 

fits in a flush-mounted switch box

Connection type: 

plug-in screw terminals

Power consumption  

when relay

is not energised: 

0.7 W