What should you do, if...?
Wiring diagram
Possible faults:
Possible causes and remedy:
S10AF does not switch on when
the power supply is switched on.
+UB pilot light (green) does not
illuminate.
- Check mains feed (fuse).
- Check safety circuit (e.g. emergency stop switch, slack cable limit switch, safety limit
switch).
- Check that connection wires are securely fixed in the terminals.
- Check fine-wire fuse inside the unit. Replace if defective. If failure occurs again, inform
your dealer.
No response when buttons are-
pressed.
- Bridge the input terminals for the external STOP button.
- Check plug-in connections of triple pushbuttons.
The door only opens in
deadman’s mode.
Set DIP 1 to ON