background image

 

 
 

com

.

tom

 

BASIC 2.0 – Start-up Guide

 

 

The com.tom BASIC device communicate with 
the web portal via Ethernet and the existing 
network infrastructure. The communication 
mechanism has a low data volume and can be 
integrated easily in the existing network infra-
structure. 

Device may only be put into service and 
operated by qualified personnel. 

The device is designed for an installation on a 
grounded 35 mm DIN Rail in dry rooms. 

 

 

 

After the installation the housing of the device is connected with 

functional earth. 

The power supply must be a grounded circuit (PELV). 

The power supply must be a limited power source according to 
EN60950-1 cap. 2.5 or the device must be provided with an anti-
surge fuse of 2 A.  

Pin Assignment 

Power Supply 

FE 

Functional earth 

GND Ground 
VCC 

24 VDC 

Serial Interface COM0 

 

RS232 

RS485 

RS422 

Pin 1 

NC 

A(-/Y) 

A(TxD) 

Pin 2 

RxD 

NC 

NC 

Pin 3 

TxD 

NC 

NC 

Pin 4 

NC 

NC 

A'(RxD) 

Pin 

5  GND GND GND 

Pin 6 

NC 

B(+/Z) 

B(TxD) 

Pin 7 

RTS 

NC 

NC 

Pin 8 

CTS 

NC 

NC 

Pin 

9 NC NC B'(RxD) 

Housing 

Connected to functional earth 

 

 

 

 

 

 
 
 
 
 
 

 

 
 

Serial Interface COM1 

 

RS232 

 

 

Pin 1 

NC 

 

 

Pin 2 

RxD 

 

 

Pin 

3 TxD  

 

Pin 4 

NC 

 

 

Pin 5 

GND 

 

 

Pin 6 

NC 

 

 

Pin 7 

RTS 

 

 

Pin 8 

CTS 

 

 

Pin 9 

NC 

 

 

Housing 

Connected to functional earth 

Ethernet Interface 

Green LED 

Link indication 

Yellow LED 

Activity indication 

LEDs 

Status A 

Freely programmable 

Status B 

Freely programmable 

Status C 

Freely programmable 

Status D 

Freely programmable 

Power 

Device is powered 

Other Interfaces 

SD card interface 

MMC/SD memory cards 

SIM card interface 

no function 

 

 
 

Getting Started 

Wire the com.tom device according to the technical data.  
Get the Getting Started documentation at www.beck-
ipc.com/gettingstarted and follow the steps described there to 
put your com.tom device into operation. 
 

General Data 

Size (W x L x H) 

46 x 103 x 63 mm 

Operating temperature 

0 to 55 °C  

Electrical shock 

Class III 

Protection rating 

IP20 

EMC emission 

IEC 61000-6-4 

EMC immunity 

IEC 61000-6-2 

Compliance 

CE, RoHS 

Electrical Data 

Supply voltage 

24 VDC (

15 %) 

Active current 

< 80 mA  
 

 

Scope of supply 

 
1 Piece 

com.tom BASIC 2.0 

1 Piece 

Start-up guide 

1 Piece 

Connector 3-pin 

 

 