Page 6 of 8
Additional assist call devices can be connected to the circuit of either one additional cancel plate or
overdoor indicator and up to 5 additional ceiling pull cords.
All system wiring should be installed to meet the appropriate parts of BS 7671 (Wiring Regulations).
Other national standards of installation should be adhered to where applicable.
Extra Low Voltage (ELV) Wiring:- Always segregate low voltage wiring from the main wiring.
4.2.2
BAKIT Kit connection to a Beacon Master Station, System
Expander Panel and Assist Call Master Station
The devices are wired to the terminals marked 0 and +, the devices are polarity sensitive, however
there are no in or out terminals and devices can be wired in any order. The cabling between the
controller and the devices is 2 core 1 mm csa flex, wired in a radial circuit up to150 m length. The circuit
is fully monitored for open and short circuit and a 10K EOL resistor should be fitted across the terminals
in the last device.
ACS Change Diagram please
Additional assist call devices can be connected to the circuit of either one additional cancel plate or
overdoor indicator and up to 5 additional ceiling pull cords.
All system wiring should be installed to meet the appropriate parts of BS 7671 (Wiring Regulations).
Other national standards of installation should be adhered to where applicable.
Extra Low Voltage (ELV) Wiring:- Always segregate low voltage wiring from the main wiring.
4.2.3
BAKIT Kit connection to BTB type B Outstation
There is the facility to connect a BAKIT kit to a type B outstation however please see below
as the wiring details are different from those previously mentioned.
The devices are wired to the terminals marked 0 and +, the devices are polarity sensitive, however
there are no in or out terminals and devices can be wired in any order. The cabling between the
controller and the devices is
2 core 1.5 mm csa fire resistant cable
to match that of the type B
outstation circuit. The circuit is extended from the terminals marked EOL Out in the type B outstation.
ACS To Alter diagram