3
A
B C
2
75.5737.12 MS21H 20201014
Page 3 of 4
GREEN
YELLOW
RED
BLACK
WHITE
RED
BLACK
WHITE
GREEN
BLUE
Installer Provided
Wire Harness
ISOLATION
MODULE
RED
BLACK
WHITE
BLUE
WIRE NUT
NO
COM
− POWER
+ POWER
NC
EAR
TH GROUND
GREEN / YELLOW
GREEN
DOOR HEADER
Isolation Module
Signal
Harness Wire
Isolation Module Wire
Door Control Terminal
To Door Control
(6-wire side)
AC/DC +
-
Red
AC/DC +
AC/DC -
-
Black
AC/DC -
COM
-
White
ACT COM
NO
-
Green
ACT NO
NC
-
Yellow
ACT NC
Earth Ground
-
Green / Yellow
Earth Ground
To MS21
(5-wire side)
COM
White
White
-
NO
Green
Green
-
AC/DC
Red
Red
-
AC/DC
Black
Black
-
Earth Ground
Blue
Blue
-
It will take approximately 10 seconds to complete the initialization sequence once powered.
Wire-nut harness wires and isolation module wires together and then connect the isolation
module wires to the door control using the chart or visual representation below.
NOTE:
From isolation module to ACT, use either green (NO) OR yellow (NC).
(A) SENSING ZONE
–
potentiometer
COUNTERCLOCKWISE – decrease (0’’ minimum)
CLOCKWISE – increase (4’’ maximum)
1
(B) AUDIBLE ALERT
– DIP-switch 1 (left)
ON – audible alert pulsed for 0.5 seconds during detection
OFF – audible alert off
(C) LED
– DIP-switch 2 (right)
ON – LED on at rest, pulsed off for 0.5 seconds during detection
OFF – LED off at rest, pulsed on for 0.5 seconds during detection
SETTINGS & ADJUSTMENTS
NOTES:
1. Maximum Sensing Zone will vary depending on size (area), orientation, and speed of object as well as environmental conditions.
WIRING (cont.)