Page 4 of 8
75.5079.10 LO21P 20221219
SETUP
1. Ensure that the On / Off / Hold Open switch is in the ON position and that the door control is
powered and operating normally.
2. Power the BODYGUARD-T and, using the Universal
Remote Control, unlock the sensor and change the
Output Configuration to a value of 2. If necessary, refer
to the BODYGUARD-T User’s Guide for programming
instructions.
3. Power the LO21P on with 12 – 24 VAC/VDC, and ensure all sensors or other devices in the
application are properly powered.
4. Observe the green LED on the BODYGUARD-T upon powering. With the door in the closed
position, the green LED should begin flashing, then stop flashing after approximately 5
seconds to indicate a successful setup for the “door closed” position.
5. Activate the door to the open position. The BODYGUARD-T should begin flashing green, then
stop flashing after approximately 5 seconds to indicate a successful setup for the “door open”
position.
If the door goes into safety swing as soon as it starts to close and you have a time delay set for
the length of the closing cycle, reverse the black and red wires to the motor input for DC units.
Correct any faults before proceeding.
If the BODYGUARD-T learns a “door closed” position, but does not execute a setup for the “door open”
position, place the door in a “hold open” position. With the Universal Remote Control, unlock the
BODYGUARD-T and (with the door in the open position) press the Magic Wand key and then 2.
The BODYGUARD-T should begin flashing green to signify a setup. If it does not, this means that improper
data is being sent for the “door open” position.
Check to ensure that data exists on the data lines leading into the BODYGUARD-T. In the “full open”
position, voltage should be approximately 9 – 12 VDC. If it is not, check the data lines (white wire on
terminal 6 and red/white wire on terminal 7) for correct voltage (see chart).
To perform a quick test by remote control to check motor wire polarity, perform the following:
1. Place the On / Off / Hold Open switch in the ON or AUTO position.
2. Activate the door and immediately walk into the BODYGUARD-T detection zone while door is open.
The door hold open at this point. Make sure there is no EAGLE activation during this time.
3. Unlock the BODYGUARD-T and press Magic Wand and 2. The green LED will begin flashing. If the
door closes while flashing green, check for correct polarity at the red and black wire from lockout.
DOOR CLOSED
DOOR OPEN
DOOR CLOSING
0 VDC
9 – 12 VDC
8 VDC