1. Generals 

1.1  General  and  safety-related  information  on  this 
operating manual 

This operating manual enables safe and proper handling of 
the product, and forms part of the device. It should be kept in 
close proximity to the place of use, accessible for staff 
members at any time. 

All  persons  entrusted  with  the  mounting,  installation,  putting 
into  service,  operation,  maintenance,  removal  from  service, 
and  disposal  of  the  device  must  have  read  and  understood 
the  operating  manual  and  in  particular  the  safety-related 
information. 

– Technical modifications reserved – 

1.2 

Symbols Used

 

 

Warning word

 

-  Type and source of danger 
-  Measures to avoid the 

danger 

 

Warning word

 

Meaning

 

 

DANGER

 

-  Imminent danger! 
-  Non-compliance will result in 

death or serious injury. 

 

WARNING

 

-  Possible danger! 
-  Non-compliance may result in 

death or serious injury. 

 

CAUTION 

 

-  Hazardous situation! 
-  Non-compliance may result in 

minor or moderate injury. 

NOTE

  –  draws  attention  to  a  possibly  hazardous  situation 

that  may  result  in  property  damage  in  case  of  non-
compliance.  

1.3 

Staff Qualification

 

Qualified  persons

 

are  persons  that  are  familiar  with  the 

mounting,  installation,  putting  into  service,  operation, 
maintenance,  removal  from  service,  and  disposal  of  the 
product  and  have  the  appropriate  qualification  for  their 
activity

All  work  with  this  product  must  be  carried  out  by  quali-
fied persons!

 

1.4 

Limitation of Liability and Warranty

 

Failure to observe the instructions or technical regulations, 
improper use and use not as intended, and alteration of or 
damage to the device will result in the forfeiture of warranty 
and liability claims. 

1.5 

Intended Use

 

-  The  Pressure  switch  iS4  with  IO-Link  interface  has  been 

developed for pressure measuring applications depending 
on  the  particular  model.  Depending  on  mechanical  con-
nection, they are suitable for a wide range of applications. 
The  pressure  switch  is  intended  for  installation  in  a  ma-
chine or system. It is the responsibility of the user to check 
whether the device is suitable for the chosen application. If 
in  doubt,  please  contact  our  sales  office.  BD  SENSORS 
cannot,  however,  assume  any  liability  for  an  incorrect 
choice or any consequences arising from this! 

-  Media  that  can  be  measured  compressed  air  and  non-

aggressive gases which are compatible with the materials 
that contact the medium. These are described in the data 
sheet. Furthermore, it must  be ensured in  each individual 
case  that  the  medium  is  compatible  with  the  parts  they 
come in contact with it. 

-  The  technical  data  listed  in  the  current  data  sheet  are 

engaging.  If  the  data  sheet  is  not  available,  please  order 
or download it from our homepage. 

 

WARNING 

 

Danger of death through incorrect 
use 

-  In order to avoid accidents, use the 

device only in accordance with its 
intended use. 

 

1.6 Package contents 

Check that all of the listed parts are included in the delivered 
package  and  have  been  supplied  in  accordance  with  your 
order: 

-  Electronic OEM Pressure Switch iS4  

-  Operating Manual  

2. Product Identification 

The  type  plate  serves  to  identify  the  device.  The  most 
important  data  can  be  taken  from  this.  The  order  code  is 
used for unique identification of your product. 

Fig. 1 Type plate

  

 

The type plate must not be removed from the device! 

3. Installation

 

3.1 Installation and safety instructions 

 

DANGER 

 

Danger of death from electric shock 

- Install the device only when the machine 
is depressurized and the power supply 
has been switched off! 

 

WARNING 

 

Danger of death from improper installa-
tion 

- Installation must be performed only by 
appropriately qualified specialist personnel 
who have read and understood the user 
manual. 

General information for oxygen use 

 

DANGER 

 

Danger of death from explosion 
through improper use of devices in-
tended for use with oxygen 

-  The following points must be observed 
in order to ensure safe handling: 

-  Make  sure  that  a  special  version  of  your  device  has 

been ordered for use with oxygen and that the expected 
device  has  been  delivered.  The  easiest  way  for  you  to 
verify this is by checking the type plate (see Fig. 1  re-
garding  this).  If  your  order  code  ends  with  the  digits 
"007",  then  your  device  is  suitable  for  oxygen  applica-
tions. 

-  When it is delivered, the device is packaged in a plastic 

bag  to  protect  it  from  contamination.  Take  note  of  the 
advice  sticker  with  the  text  "Device  for  oxygen;  unpack 
immediately  before  installation"!  Also  note  that  contact 
with  skin  should  be  avoided  when  unpacking  and  in-
stalling  the  device  so  as  to  avoid  leaving  grease  resi-
dues on the device. 

-  The relevant provisions concerning explosion protection 

must be met during installation. Also check whether ap-
proval as intrinsically safe equipment is required in addi-
tion to suitability for oxygen. (This is not the case for the 
device as supplied!) 

-  Please note that the entire system must comply with the 

requirements  of  the  BAM  (German  Federal  Institute  for 
Materials Research and Testing, DIN 19247). 

-  Pressure  transmitters  designed  for  use  without  seals 

are recommended for oxygen applications > 25 bar.  

-  Pressure  transmitters  with  FKM  (Vi  567)  sealing  rings: 

Maximum  permitted  values:  25  bar  /  150°  C   
(BAM approval). 

 

Please  treat  this  highly  sensitive  electronic  measuring 
instrument  carefully,  both  when  packed  and  when  un-
packed! 

 

No  modifications  or  alterations  may  be  made  to  the 
device. 

 

Do not throw or drop the device! 

 

Only  remove  the  packaging  and,  if  applicable,  the 
protective cap from the device shortly before its installa-
tion, so as to avoid damaging the diaphragm. Be sure to 
retain the supplied protective cap! 

 

Fit the protective cap back over the diaphragm immedi-
ately after dismounting the device. 

 

Treat  the  unprotected  diaphragm  with  extreme  care;  it 
can be damaged very easily. 

 

Do  not  apply  any  force  to  install  the  device  so  as  to 
avoid damaging the device and the system! 

 

When installing outdoors or in humid environments, the 
following points should be noted: 

-  The device should be electrically connected immediate-

ly after installation to ensure that no moisture is able to 
penetrate into the plug connector, if this is not possible, 
the  ingress  of  moisture  must  be  prevented  by  using  a 
suitable  protective  cap.  (The  protection  class  specified 
in the data sheet applies to the connected device.) 

-  Select an installation position that allows splashed water 

and  condensation  to  drain  away.  Ensure  that  sealing 
surfaces are not exposed to standing liquid! 

-  Install  the  device  such  that  it  is  protected  from  direct 

sunlight. In the worst case, direct sunlight may result in 
the  maximum  permissible  operating  temperature  being 
exceeded, which can then damage the device or affect 
its ability to function correctly. If the internal pressure in 
the device rises, this could also cause temporary meas-
urement errors. 

 

Take care that the pressure connector is not subjected 
to  any  mechanical  stresses  higher  than  that  permitted, 
since this could cause the characteristic to shift or result 
in  damage.    This  applies  especially  to  very  small  pres-
sure ranges, as well as to devices with a pressure con-
nector made of plastic. 

 

In the case of hydraulic systems, orient the device such 
that the pressure connector faces upwards (for venting). 

 

Provide  a  cooling  section  when  using  the  device  in 
steam lines. 

 

If  there  is  a  risk  that  a  device  installed  outdoors  might 
be  damaged  by  lightning  strike  or  overvoltage,  we  rec-
ommend  the  provision  of  overvoltage  protection  be-
tween  the  power  supply  unit  or  control  cabinet  and  the 
device. 

 

If  the  device  is  installed  with  the  pressure  connector 
facing upwards, make sure that no liquid runs down the 
housing.  This  could  result  in  moisture  and  dirt  blocking 
the gauge reference in the housing and cause malfunc-
tions.  If  necessary,  remove  any  dust  and  dirt  from  the 
edge of the screw joint of the electrical connector. 

3.2 General installation instructions 

-  Carefully  remove  the  device  from  its  packaging  and 

dispose of the packaging properly. 

-  Then  proceed  as  described  in  the  following  installation 

instructions. 

3.3 Installation steps for internal thread G1/8" 

-  Use  a  suitable  seal  for  sealing,  e.  g.  Teflon  strip,  flat 

gasket or O-ring, on the screwed end of the counterpart. 

-  Ensure  that  the  surface  of  the  taking  part  is  perfectly 

smooth and clean. 

-  Tighten  the  counterpart  with  a  wrench  (max.  torque 

3 Nm). 

3.4 Installation steps for internal thread M5 

-  For  sealing  use  an  O-ring  that  fits  properly  into  the 

groove. (O-ring is not included in the scope of delivery) 

 -  Ensure  that  the  surface  of  the  counterpart  is  perfectly 

smooth and clean. 

-  Screw  the  counterpart  (e.g.  screw  connection,  quick 

coupling) by hand into the pressure switch. 

-  Tighten  the  counterpart  with  a  wrench  (max.  torque 

1 Nm). 

4. Electrical Installation 

 

WARNING 

Danger of death from electric shock 

- Switch off the power supply before 
installing the device. 

 

Electrically  connect  the  device  in  accordance  with  the 
specifications  given  on  the  type  plate,  the  following  pin 
assignment table and the connection diagram. 

Pin configuration: 

Electrical connection 

M8x1  

(4-pin) 

(L+) 

(L-) 

C/Q 

 
Supply – 

IO-Link (COMx) / SIO 



4

 

Shield 

housing 

Wiring diagram: 

SIO / IO-Link (COMx)-System

 

 

 

If  possible,  use  a  shielded  and  twisted  multicore  cable 
for the electrical connection. 

5. Commissioning 

 

Before  using  the  device  for  the  first  time,  check  that  it 
has been properly installed, and make sure that it does 
not show any visible defects. 

 

The device may by commissioned only by appropriately 
qualified specialist personnel who have read and under-
stood the user manual. 

 

The  transmitter  shall  be  supplied  by  Limited  Energy 
Source (per UL 61010) or NEC Class 2 Power Source. 

6. IO-Link Interface  

6.1 General device information 

Baud rate 

COM2 (38,4 kbit/s) 

Input process data length 

2 byte 

Minimum cycle time 

5 ms 

IO-Link version0000000000 

V 1.1 

SIO-Mode 

yes 

6.2 SIO mode (standard IO mode) 

In  this  mode  the  sensor  operates  like  a  normal  pressure 
sensor  with  standard  output  signals.  The  digital  output  is 
always on Pin 4 of the connector plug or over green cable. 

6.3 IO-Link mode (communication mode) 

The pressure sensor switches to the IO-Link communication 
mode,  when  it  operates  under  an  IO-Link  master.  IO-Link 
communication  is  only  possible  over  Pin  4  of  the  connector 
plug or over green cable. 

6.4 Process data 

The process data length of the sensor is 16 bits. The switch 
state  (BCD1)  as  well  as  the  current  measured  values  are 
transmitted.  The  14  bits  of  the  measured  value  are  scaled 
according to the measuring range. 

15 bit 

14…2 

Signed 

Bit 

Measured 

value 

BDC1 / Output 1 

 

6.5 Error codes 

Error Code 

Description 

0x8011 

Index not available 

0x8012 

Subindex not available 

0x8023 

Access Denied 

0x8030 

Parameter Value out of Range 

0x8033 

Parameter length overrun 

0x8034 

Parameter length under run 

6.6 Event codes 

 

 

Event-
Codes 
IO-Link 
1.1 

Event-
Codes 
IO-Link 
1.0 

Device 
status 

Type 

No malfunc-
tion 

0x0000 

0x0000 

Notifica-
tion 

General 
malfunction. 
Unknown 
error 

0x1000 

0x1000 

Error 

Process 
variable range 
over-run. 
Process Data 
uncertain 

0x8C10 

0x8C10 

Warning 

Process 
variable  range 
under-run. 
Process  Data 
uncertain 

0x8C30 

0x8C10 

Warning 

 

6.7 Parameter data 

The parameter data of the pressure switch correspond to the 
Smart Sensor Profile. The data can be found in the product 
data sheet or parameter overview, see section 13. 
 

7. Decommissioning 

 

 

 

 

WARNUNG 

 

Danger of injury from media escap-
ing under pressure 

- Dismount in an orderly fashion when 
the machine is depressurized and the 
power supply has been switched off. 

- Check whether the medium needs to 
be drained before dismounting! 

 

 

WARNUNG 

 

Danger of injury from the measured 
medium 

- Depending on the measured medi-
um, suitable precautions should be 
taken, e.g. protective gloves, goggles. 

 

8. Maintenance 

The  device  is,  in  principle,  maintenance  free.  If  necessary, 
the housing of the device may be cleaned with a damp cloth 
and  a  non-aggressive  cleaning  solution  while  it  is  switched 
off.  

With certain media may, however, deposits or contamination 
may  accumulate  on  the  diaphragm.  The  specification  of 
appropriate  maintenance  intervals  for  inspection  is  recom-
mended  in  this  case.  Once  the  device  has  been  properly 
decommissioned,  the  diaphragm  can  normally  be  cleaned 
with  a  non-aggressive  cleaning  solution  and  a  soft  brush  or 
sponge.  Care  should  be  taken  while  doing  so.  If  the  dia-
phragm  is  covered  in  lime  scale,  decalcification  by  BD 
SENSORS  is  recommended.  See  the  Servicing/Repair 
section with regard to this. 

 

Incorrect  cleaning  can  result  in  irreparable  damage  to 
the  measuring  cell.  For  this  reason,  you  should  never 
use  sharp  objects  or  compressed  air  to  clean  the  dia-
phragm. 

 

9. Servicing/Repair 

9.1 Recalibration 

It  is  possible  that  the  offset  value  or  the  scaling  value  may 
shift  during  the  lifetime  of  the  device.  This  is  indicated  by  a 
deviation in the output signal value with reference to the set 
measurement range start or end values respectively. If either 
of  these  two  phenomena  should  occur  after  a  prolonged 
period  of  use,  recalibration  is  recommended  in  order  to 
ensure a continued high level of accuracy.  

9.2 Return 

Whenever  the  device  is  returned,  no  matter  whether  for 
recalibration, decalcification, modification or repair, it must be 
carefully  cleaned  and  packed  such  that  there  is  no  risk  of 
breakage.  The  device  must  be  accompanied  by  a  notice  of 
return giving a detailed description of the fault. If your device 
has  come  into  contact  with  pollutants,  then  a  notice  of 
decontamination  will  also  be  needed.  You  can  find  the 
relevant  templates  on  our  website  at 

www.bdsensors.de

Should  you  send  in  your  device  without  a  notice  of  decon-
tamination  and  doubts  with  regard  to  the  medium  used 
should  arise  in  our  service  department,  repair  work  will 
commence  only  once  an  appropriate  notice  has  been  re-
ceived. 

 

CAUTION 

 

Danger of injury from pollutants 

- If the device has come into contact with 
pollutants, wear suitable protective cloth-
ing, e.g. gloves, goggles, when cleaning 
it. 

 

 

10. Disposal 

The  device  must  be  disposed  of  in  accord-
ance  with  European  Directives  2002/96/EC 
and  2003/108/EC  (Waste  Electrical  and 
Electronic  Equipment).  Waste  electrical 
products  may  not  be  disposed  of  with 
household waste! 

 

Depending  on  the  medium  used,  residues 
on  the  device  may  constitute  a  hazard  to 
the environment.  You should therefore take 

appropriate  precautions  if  necessary  and 
dispose of the device properly. 

11. Guarantee Conditions 

The guarantee conditions are subject to the statutory warran-
ty period of 24 months, starting from the date of dispatch. No 
warranty claims will be accepted if the device has been used 
improperly,  modified  or  damaged.  The  warranty  does  not 
cover  damaged  diaphragms.  Warranty  cover  also  excludes 
any claims for defects that have arisen as a result of normal 
wear. 

12. Declaration of conformity / CE 

The  supplied  device  fulfills  the  statutory  requirements.  The 
relevant  directives,  harmonized  standards  and  documents 
are  listed  in  the  EU  Declaration  of  Conformity  applicable  to 
the  product.  This  can  be  found  at  http://www.bdsensors.de. 
In addition, the operational safety of the  device is confirmed 
by the CE mark on the type plate. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Order code 

Pin configuration 

   Type designation 

Supply 

  Measure- 
  range 

Signal 

  Serieal- 
  number 