The height of the base frame must be higher than the height of the
heaviest snowfalls. This measure helps to protect the exchanger from
snow and prevent the formation of ice during the defrosting operation.
For regions where heavy snowfalls occur, raise the above-ground
protection by at least 200 mm compared with the average depth of the
covering of snow.
Caution
If the outside temperatures become negative, take the
necessary precautions to prevent the risk of freezing in the
evacuation pipes.
Prevent any risk of the condensates freezing in a passing-by
zone.
Fig.22
Installation of a single outdoor unit or several outdoor units
MW-6000252-1
1
2
1. Always install the outdoor unit as far as possible from the
thoroughfare as the condensates discharge may freeze, causing a
potential hazard (sheet of black ice).
2. Place the outdoor units beside each other and not on top of each
other to prevent the condensates from the lower unit to freeze.
Position of the display
Install the display against an internal wall at eye level in the room chosen.
Locations in the room not recommended:
Do not install the display in a place subject to excessive humidity or oil
vapours (such as a kitchen or bathroom).
Do not install the display in the vicinity of powerful electrical appliances
in order to prevent any interference.
5.3
Transport
5.3.1
Precautions for transporting the domestic hot water tank
Store and transport the domestic hot water tank packed and drained of
water.
Permissible ambient transport and storage temperatures: -20°C to +
60°C.
Fig.23
MW-4000120-3
Fig.24
Transporting the domestic hot water
tank
MW-4000121-1
5 Before installation
7740321 - v04 - 03122019
SPC Split
37