5.7
Positioning the cassette unit
5.7.1
Installation location
Caution
Ensure that the installation location is able to take four times the
unit weight and capable of bearing vibration for long periods.
Select a suitable position in order to achieve a uniform air temperature
in the place of installation.
Adhere to the minimum distances between other objects and obstacles.
Make sure that there is space to install the condensate pipe with a slope
on the chosen location.
Fig.181
MW-6070070-01
1500
2000
4000
1
3
2
1
1500
2500
50
1 Indoor unit
2 Lighting
3 Fan
5.7.2
Suspending the unit
Important
Ensure that the installation location is able to take four times the
unit weight and capable of bearing vibration for long periods.
Ensure the condensate can properly be drained. Install the unit
slightly sloped towards the drain tap.
1. Mount the fasteners of the indoor unit in one of the following ways:
with a dowel on which the suspension bolt is screwed.
with a suspension rod fixed directly on the hard structure (steel or
wood).
Fig.180
MW-6070069-01
1500
1500
1500
1500
MW6020094-01
5 Installation
en
7798731 - v01 - 18112021
159