C

ALIBRATION

 M

ODE

:

Proceed as follows to enter “calibration mode” on the boiler control panel and calibrate
the gas value:

1. Turn the control knobs 6 and (fig. 1) 7 fully counter-clockwise to their

minimum positions as shown below.

2. Starting in this position, quickly turn control knob 7 twice, consecutively,

clockwise approximately a 

 turn as shown below in fig. 2.

Note: LED’s 2 and 3 (fig. 4) flash alternately and the display alternates the message
“SF” and the boiler output temperature every five seconds (fig. 3).

3. Now turn knob 6 to adjust the fan speed to a setting between minimum

thermal power (0%) and maximum thermal power (100%).

Note: In “calibration mode”, the display alternates between the message “P” and
the boiler output temperature about every 5 seconds. (fig. 4)

4. Calibration mode remains active for 20 minutes. To exit “calibration mode”

before this time simply turn control knob 7 twice, consecutively, clockwise
approximately a 

 turn as shown in fig. 2.

Note: This function is interrupted if the central heating delivery temperature
reaches its MAX. SETPOINT.

P

ROCEED AS FOLLOWS TO CALIBRATE THE GAS VALVE

:

1. Ensure your combustion analyzer is set to NG, insert the flue probe into the flue

opening on the top of the boiler, after removing the two flue test port plugs.

2. Calibrate maximum thermal power by turning knob 6 clockwise to max. With the

boiler operating at max. output, check the value for CO

measured in the flue is

8.7%

. If necessary, turn the adjustment screw, or “V” screw, on the gas valve.

Turn clockwise to reduce the CO2 level or counter-clockwise to increase it.

3. Calibrate minimum thermal power. With boiler operating at minimum output by

turning knob 6 counter-clockwise to minimum setting. Check the CO

value

measured in the flue to 

8.4% 

CO

2

. If necessary adjust the “K” screw (4mm hex) on

the gas valve. 

Turn clockwise to increase the CO

level or counter-clockwise

to reduce it.

Note: Allow time between adjustments for your combustion analyzer to sense the adjusted for your
combustion analyzer to sense the adjusted CO

level. The boiler is now ready for normal operation using NG 

gas and can be returned to the service mode by turning control knob 7.

B

AXI

 L

UNA

 HT 1.650 S

ETUP

 N

ATURAL

 G

AS

Luna HT 1.650 Setup Natural Gas

Содержание LUNA HT 1.330

Страница 1: ...ers appears on the display 2 Simultaneously press keys 1 and 2 for approximately 3 seconds Parameter 504 will appear on the display 3 Press key 1 or 2 to scroll through the list of parameters 4 To cha...

Страница 2: ...temperature reaches its MAX SETPOINT PROCEED AS FOLLOWS TO CALIBRATE THE GAS VALVE 1 Ensure your combustion analyzer is set to NG insert the flue probe into the flue opening on the top of the boiler a...

Страница 3: ...alibrating the gas valve 1 Turn the adjusting screw or V screw 2 5 mm hex on the gas valve all the way clockwise until the V is bottomed out Then turn the V screw eleven complete revolutions counter c...

Страница 4: ...follows to access these parameters 1 Simultaneously press keys 1 and 4 on the QAA73 controller for approximately 3 seconds The message Initializing BMU parameters appears on the display 2 Simultaneou...

Страница 5: ...ry temperature reaches its MAX SETPOINT PROCEED AS FOLLOWS TO CALIBRATE THE GAS VALVE 1 Ensure your combustion analyzer is set to LPG insert the flue probe into the flue opening on the top of the boil...

Страница 6: ...BAXI LUNA HT 1 650 SETUP PROPANE Luna HT 1 650 Setup Propane...

Страница 7: ...ted parameter press key 3 4 to decrease or increase the value respectively 5 Press key 5 to enter the new values and exit programming of the boiler s electronic main board Les param tres qui peuvent t...

Страница 8: ......

Страница 9: ......

Страница 10: ......

Страница 11: ......

Отзывы: