FIGURE 6-28 - Flue Terminal Location
All vent pipe and combustion air pipe and fittings shall comply with the following:
Use only manufacturer approved venting materials or venting materials primer and glue approved to: ULC S636 in Canada, or UL
1738 in the U.S.
Materials used in the U.S. shall comply with Authority having jurisdiction and in absence of such with: ANSI/ASTM D1785, ANSI/
ASTM F441, ANSI/ASTM F493.
INSIDE CORNER
DETAIL
G
V
H
D
A
E
B
L
C
B
V
B
Fixed
Closed
V
I
V
F
V
Fixed
Closed
Operable
Operable
M
V
B
V
K
J
B
V
VENT TERMINAL
AIR SUPPLY INLET
AREA WHERE TERMINAL IS
NOT PERMITTED
Vent Termination Minimum Clearances
US Installations
Canadian Installations
A
Clearance above grade, veranda, porch, deck, or balcony
12" (305 mm)
12" (305 mm)
B
Clearance to window or door that may be opened
12" (305 mm)
3 ft. (0.9 m)
C
Clearance to permanently closed window
*12" (305 mm)
*12" (305 mm)
D
Vertical Clearance to ventilated soffit located above the terminal within a
horizontal distance of 2 feet (610 mm) from the center line of the terminal
18" (457 mm)
18" (457 mm)
E
Clearance to unventilated soffit
18" (457 mm)
18" (457 mm)
F
Clearance to outside corner
9" (229 mm)
9" (229 mm)
G
Clearance to inside corner
36" (456 mm)
36" (456 mm)
H
Clearance to each side of center line extended above meter/
regulator assembly
3 ft. (0.9 m) within a
height of 15 ft. (4.5
m) above the meter/
regulator assembly
3 ft. (0.9 m)
I
Clearance to service regulator vent outlet
3 ft. (0.9 m)
3 ft. (0.9 m)
J
Clearance to non-mechanical air supply inlet to building or the
combustion air inlet to any other appliance
12" (305 mm)
3 ft. (0.9 m)
K
Clearance to mechanical air supply inlet
*3 ft. (0.9 m)
6 ft. (1.8 m)
L
Clearance above paved sidewalk or paved driveway located on
public property
*7 ft. (2.1 m)
7 ft. (2.1 m) †
M
Clearance under veranda, porch, deck or balcony
*12" (305 mm) ‡
12" (305 mm)‡
† A vent shall not terminate directly above a sidewalk or paved drive-
way that is located between two single family dwellings and serves
both dwellings.
*For clearances not specified in ANSI Z223.1/NFPA 54
or CSA B149.1, clearance will be in accordance with
local installation codes and the requirements of the
gas supplier and these installation instructions.
‡ Permitted only if veranda, porch, deck or balcony is fully open on a
minimum of one side beneath the floor.
Note:
Local Codes or Regulations may require different clearances. Flue terminal must be exposed to external air and position
must allow the free passage of air across it at all times. In certain weather conditions the terminal may emit a plume of steam. Avoid
positioning terminal where this may cause a nuisance.
Содержание LUNA DUO-TEC 1.48 GA
Страница 39: ...39 240012485 REV C 06 30 2019 INSTALLER Section en WIRING DIAGRAM MODEL 1 48 GA...
Страница 40: ...40 240012485 REV C 06 30 2019 INSTALLER Section en WIRING DIAGRAM MODEL 60 GA...
Страница 99: ...INSTALLER Section fr 99 240012485 REV C 06 30 2019 SCH MA DE C BLAGE MOD LE 1 48 GA...
Страница 100: ...INSTALLER Section fr 100 240012485 REV C 06 30 2019 SCH MA DE C BLAGE MOD LE 60 GA...