Baxi Geoflo

Single Compressor Compact Heat Pump

Please keep these instructions in a safe place.

If you move house, please hand them over to the next occupier

Operation Installation & Maintenance

Instructions

Содержание Geoflo

Страница 1: ...UK Ltd 2006 Baxi Geoflo Single Compressor Compact Heat Pump Please keep these instructions in a safe place If you move house please hand them over to the next occupier Operation Installation Maintenance Instructions ...

Страница 2: ... reserved No part of this publication may be reproduced or transmitted in any form or by any means or stored in any retrieval system of any nature including in any database in each case whether electronic mechanical recording or otherwise without the prior written permission of the copyright owner except for permitted fair dealing under Copyrights Designs and Patents Act 1988 Applications for the ...

Страница 3: ...uld be taken when moving it Check the appliance for transport damage Under no circumstances should a damaged appliance be operated or installed It is dangerous to modify this appliance in any way Ensure that the appliance does not stand on the electrical supply cable If the supply cable is damaged it must be replaced Ensure that the appliance and any metal pipes are properly earthed A water treatm...

Страница 4: ...g Heateam please have the following information to hand Geoflo system serial number Geoflo system model number Your installer name address details and contact details Proof of purchase if you do not have the Geoflo serial number What this warranty covers Free of charge repair or replacement of components found to be faulty from manufacture Free of charge replacement of the complete assemblies excl...

Страница 5: ...5 Baxi Heating UK Ltd 2006 Technical Data ...

Страница 6: ...erfloor pressure gauge reads at least 0 3 bar If the pressure is lower than this find the mains cold water supply valve which is probably near your underfloor heating manifold fully until the gauge reads at least 1 8 bar at which point a click will be heard Close the mains cold water supply valve fully If you can t find this valve or when you open it the gauge reading does not increase call your i...

Страница 7: ...7 Baxi Heating UK Ltd 2006 Operating Instructions Trouble shooting P Pr rg g S Se el l ...

Страница 8: ...8 Baxi Heating UK Ltd 2006 Elevation of typical installation ...

Страница 9: ...9 Baxi Heating UK Ltd 2006 Recommended Installation Clearances All dimensions in millimetrs ...

Страница 10: ...10 Baxi Heating UK Ltd 2006 Hood Removal Clearances All dimensions in millimetrs ...

Страница 11: ...11 Baxi Heating UK Ltd 2006 ...

Страница 12: ...12 Baxi Heating UK Ltd 2006 ...

Страница 13: ...13 Baxi Heating UK Ltd 2006 Slinky Manifold Connections ...

Страница 14: ...14 Baxi Heating UK Ltd 2006 Pumbing Connections ...

Страница 15: ...15 Baxi Heating UK Ltd 2006 Output Pump Bleed Port ...

Страница 16: ...nd it does not absorb at least 1 kW then it will not be suitable In addition the pump needs to have high flow at least 60 litres per minute against a pressure of at least 1 bar To achieve this a multi stage type of pump is needed which is different to normal types of water pump Where can I get hold of a suitable purge pump We recommend the Clarke CPE130SS part no 051010379 from www machinemart co ...

Страница 17: ...17 Baxi Heating UK Ltd 2006 Purging the Ground Arrays ...

Страница 18: ...18 Baxi Heating UK Ltd 2006 Underfloor Heating Wiring Connections Single Manifold smaller building Multiple Manifold larger building ...

Страница 19: ...19 Baxi Heating UK Ltd 2006 Control Box Layout ...

Страница 20: ...20 Baxi Heating UK Ltd 2006 Wiring Connections ...

Страница 21: ...ion The wires can be connected either way round Avoid routing this cable with any other cables to prevent interference 10 Check and rectify any leaks that may be in the plumbing system 11 Remove the plastic blanking plugs and connect the purge pump to the fill and purge ports on the Slinky Manifold see Purging the ground arrays Keep the isolating valve to the heat pump closed The purge ports can b...

Страница 22: ...re so that any leaks will immediately become apparent 21 In order to activate the software controller both the ground and underfloor circuits must be taken above 1 8 bar water pressure 22 Remove the purging equipment and the handles from the valves on the manifold to ensure they cannot be inadvertently operated and place the plastic blanking plugs back in the slinky manifold 23 Find the cold fill ...

Страница 23: ...Notes 23 Baxi Heating UK Ltd 2006 Notes ...

Страница 24: ... 261 Website www baxi co uk e oe company All descriptions and illustrations provided in this leaflet have been carefully prepared but we reserve the right to make changes and improvements in our products which may affect the accuracy of the information contained in this leaflet All goods are sold subject to our standard Conditions of Sale which are available on request ...