Caution
Secure the cable with the cable clamp provided. Be careful that
you do not invert any of the wires.
6.8.2
Recommended cable cross section
The electrical characteristics of the mains power supply available must
correspond to the values given on the data plate.
The cable will be carefully chosen according to the following information:
Maximum intensity of the outdoor unit. See table below.
Distance of the appliance from the original power supply.
Upstream protection.
Neutral operating conditions.
Important
The maximum permissible current on the power supply cable of
the indoor unit must not exceed 6 A.
Tab.29
Appliance
Power supply type
Cable cross section
(mm
2
)
Circuit breaker curve
C (A)
Maximum amperage
(A)
Indoor unit
Single phase
Cable provided (3 x
1.5)
10
-
Electrical back-up
Single phase
3 x 6
32
-
Three phase
5 x 2.5
16
-
-
2 x 0.75
-
-
AWHP 4.5 MR
Single phase
3 x 2.5
16
12
AWHP 6 MR-3
Single phase
3 x 2.5
16
13
AWHP 8 MR-2
Single phase
3 x 4
25
17
(1) Connection cable linking the outdoor unit to the indoor unit
6 Installation
7762758 - v05 - 19082020
37