Technical description of the burner
3.3
Burner description (Fig. 2)
1
Ignition electrodes
2
Combustion head
3
Screw for combustion head adjustment
4
Screw for fixing fan to flange
5
Slide bars for opening the burner and inspecting the com-
bustion head
6
Safety solenoid valve
7
Pump
8
Air inlet to fan
9
Air gate valve
10 Hydraulic cylinder for regulation of the air gate valve in 1st
and 2nd stage positions.
When the burner is not operating the air gate valve is fully
closed in order to reduce heat dispersion from the boiler due
to the flue draught which draws air from the fan suction inlet.
11 Fan pressure test point
12 Boiler mounting flange
13 Flame stability disk
14 Electrical motor
15 Extensions for slide bars 5)
16 Ignition transformer
17 Motor contactor and thermal cut-out with reset button
18 1st and 2nd stage valve assembly
19 Terminal strip
20 Two switches:
- one "burner off - on"
- one for "1st - 2nd stage operation"
21 Fairleads for wiring carried out by the installer
22 Control box with lock-out pilot light and lock-out reset button
23 Flame inspection window
24 Pump pressure adjustment
25 Photoresistor for flame presence control
26 Sockets for electrical connections
Two types of burner failure may occur:
Control box lock-out
: if the control box 22)(Fig. 2) pushbutton
(red led) lights up, it indicates that the burner is in lock-out. To re-
set, hold the pushbutton down for between 1 and 3 seconds.
Motor trip
: release by pressing the pushbutton on thermal cut-
out 17)(Fig. 2).
3.3.1
Weight (Tab. A)
- approximate measurements
•
The weight of the burner complete with its packaging is
shown in table (Tab. A)
Tab. A
D3288
Fig. 2
D3313
kg
TECNO 70-L
43,5
TECNO 100-L
46,5
TECNO 130-L
51,5