9.2 Fitting to wall.
!
Fit the flue tubes firmly over the
spigots at the rear of the fire. Make sure
that the seam on the flue tube is not at
the bottom. Push on until the outer (air)
tube just covers the slots in the appliance
outer spigot (See figure 13).
!
Secure the flue to the fire by drilling
through the outer flue tube and outer
spigot at a distance of between 6mm &
7mm from the cut end of the outer flue
tube and securing with the two no.6 self
tapping screws supplied (See figure 13).
!
Seal the flue unit all round the circumference of the outer spigot with the tape
supplied.
!
Timber frame buildings: Offer the fire complete with flue unit through the insulating
sheet (mentioned in section 8.3). Fit a drip collar round the flue positioned so that it will
be located in the centre of the wall cavity (See figure 12b). The drip collar can be made
by wrapping a non-corrosive wire round the flue or moulding a bead of mastic round
the flue.
Page 23
INSTALLER GUIDE
©
Baxi Heating U.K. Limited 2007.
Figure 12b. Flue unit installation - Timber framed building.
Figure 13. Flue securing