Software messages
Message
Cause / solution
OVR
The electromagnetic or acoustic signal is too high
during acoustic pin-pointing. As a result only your
approximate position in relation to the cable
route can be displayed (left or right of the cable
route).
The gain or output voltage may be set too high.
Manual gain:
»
Reduce the signal gain or the volume.
If the message still appears or automatic gain is
selected:
»
Reduce the output voltage on the SSG.
Note:
Another reason the message may be displa-
yed is that the fault is in the immediate vicinity.
No AGP
connected
The AGP is not switched on.
»
Switch on the AGP.
The rechargeable or non-rechargeable batteries
of the AGP are too weak.
»
Charge or replace the rechargeable batteries,
or replace the non-rechargeable batteries.
protrac® pin-pointing system
822-186-4