Diagnosis
Parameter manual
b maXX
BM5800
Document No.: 5.16029.03
Baumüller Nürnberg GmbH
682
3.10
6.38
Motor total voltage smoothed
Calculated total voltage smoothed at motor.
For the calculation the dead time voltages are compensated with 100%, independent of
the value of the dead time compensation factor
, i.e. it doesn't matter if the dead
time compensation in the motor is active or not.
The parameter is smoothed with the time constant 1,25 ms.
The unit of the parameter is [V], phase-to-phase voltage effective.
6.39
Motor I
2
t warning threshold
Settable warning threshold for the motor I
2
t monitoring (see
Motor I
2
t actual val-
ue).
If the motor I
2
t actual value
exceeds the warning threshold, the warning 219
"Warning threshold motor I
2
t exceeded" is generated. With a fixed hysteresis of 10% be-
low the warning threshold the warning is withdrawn again.
If the value for the warning threshold is 0, there is no warning.
See also
Overload monitoring of the motor (I
Standardization:
100%
Maximum thermal load of the motor
6.42
Smoothing time electr. motor power display
Smoothing time constant for the motor real power display
6.43
Motor I
2
t monitoring mode
The accordant implementation to calculate the l
2
t value of the motor must be selected.
Generally, the parameter is assigned to zero (speed-dependent monitoring is deactivated
and the monitoring of the total current is activated). See
Overload monitoring of the mo-
NOTE!
If the power indication
>
6.32
<
is evaluated and PWM frequency changes are made
during operation, the adaption of the dead time compensation must be activated after
the PWM frequency (see
bit 3) independent of the dead time compensation
being active in the motor control or not (see
).
Содержание b maXX BM5800
Страница 10: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 10 of 814 Contents ...
Страница 724: ...Monitoring Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 724 of 814 3 11 ...
Страница 756: ...Error descriptions Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 756 of 814 4 5 ...
Страница 800: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 800 of 814 ...
Страница 808: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 808 of 814 ...
Страница 814: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 814 of 814 Notes ...
Страница 815: ......