Configuration
Parameter manual
b maXX
BM5800
Document No.: 5.16029.03
Baumüller Nürnberg GmbH
66
3.4
129.9
IGBT dead time
Dead time for the power unit transistors.
129.10
Min. pulse suppression
Minimum pulse suppression is used to prevent extremely short duty cycles for pulse width
modulation, such as may occur when outputting large voltages. Instead of generating ex-
tremely short On/Off switching pulses, the switching state of the IGBTs is extended to the
next PWM period. This will further increase the maximum possible voltage setting. PWM
voltage pulses that are shorter than the parameter value will be suppressed.
129.11
Current sampling time offset
This parameter determines the starting time of the current measurement. For current con-
trol, the fundamental of the motor currents should be measured if possible. The harmon-
ics, which result from, among other things, the switching edges of the PWM, can distort
the measurement. The parameter can be used to take account of time-related influences
such as, e.g., the time constant of the analog current filter.
129.12
Nominal current 2 kHz
129.13
Nominal current 4 kHz
129.14
Nominal current 8 kHz
129.15
Nominal current 16 kHz
Nominal current of converter at the corresponding PWM switching frequency
The value in this parameter applies to the required operating conditions. See chapter
"Technical data" of the device's operating manual.
The instantaneous nominal current of the power unit dependent of the PWM frequency
entry
If operating conditions are changed and after current derating, the continuous current is
displayed in parameter
provided that the PU-overload monitoring is executed
via temperature model. See "Status PU temperature model"
.
Содержание b maXX BM5800
Страница 10: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 10 of 814 Contents ...
Страница 724: ...Monitoring Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 724 of 814 3 11 ...
Страница 756: ...Error descriptions Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 756 of 814 4 5 ...
Страница 800: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 800 of 814 ...
Страница 808: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 808 of 814 ...
Страница 814: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 814 of 814 Notes ...
Страница 815: ......