![Baumuller b maXX BM5800 Скачать руководство пользователя страница 525](http://html.mh-extra.com/html/baumuller/b-maxx-bm5800/b-maxx-bm5800_parameter-manual_2711380525.webp)
Description of the Software Modules and Parameters
Parameter manual
b maXX
BM5800
Document No.: 5.16029.03
525
3
121.21
Command positive stop drive
Command parameter to start and stop the command "Moving to positive stop"
121.22
Status positive stop drive
Status of the command "Moving to positive stop"
Notes:
Bit 0:
The bit is set as soon as the command is recognized by the drive and activated.
Bit 4:
Monitoring of the positive stop generates error message
The bit is set in case the positive stop was reached (bit 10 = 1) and the position actual
value of the drive is out of the symmetric monitoring window
of the positive
or the N=0 message is not available. The selection between
both monitoring possibilities "monitoring window" or "N=0 message" is set in
in bit 0-1.
Bit 5:
Error - Moving to positive stop not possible
The bit is set in case the command cannot be started because of the current operation
state. The error is also generated if the master-slave torque coupling or the gantry func-
tion is active.
The bit 0 "Positive stop drive active" of
remains 0 in this case.
Bit
Meaning
0
0: Switch off command "Moving to positive stop"
1: Activate command "Moving to positive stop"
15 … 1
Reserved
Bit
Meaning
0
1: Moving to positive stop active
3 ... 1
Reserved
4
1: Error – monitoring of the positive stop generates error message
5
1: Error – command "Moving to positive stop" not possible
6
1: Error – command aborted at positive stop
7
Reserved
8
1: N=0-message
9
1: Message "Clamping torque reached"
10
1: Message "Positive stop reached"
15 ... 11
Reserved
Содержание b maXX BM5800
Страница 10: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 10 of 814 Contents ...
Страница 724: ...Monitoring Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 724 of 814 3 11 ...
Страница 756: ...Error descriptions Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 756 of 814 4 5 ...
Страница 800: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 800 of 814 ...
Страница 808: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 808 of 814 ...
Страница 814: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 814 of 814 Notes ...
Страница 815: ......