Monitoring functions
Instruction handbook
b maXX
BM5500, BM5600, BM5700
Document No.: 5.13008.10
Baumüller Nürnberg GmbH
238
10.2
10.2 Monitoring functions
Monitoring function
Warning/error
Wa
rn
in
g
Error
Ad
ju
st
ab
le
thr
esh
old
Ad
ju
st
ab
le
reaction
Re
ac
ti
on
pulse
inhibit
Mains voltage
Mains undervoltage
X
X
-
-
X
Mains overvoltage
X
X
-
-
X
Phase monitoring
Phase failure
X
X
-
-
X
Mains failure
X
X
X
-
X
1)
Ground fault
Fault current to ground
-
X
-
-
X
Overcurrent
Motor overcurrent
-
X
-
-
X
DC link
DC link overvoltage
-
X
-
-
X
DC link relative undervoltage
X
X
-
-
X
Overload monitoring
Peak current not possible at this
time
X
-
-
-
-
Heat sink temperature
Temperature > threshold 1
X
-
X
-
-
Temperature > switch-off threshold
-
X
-
-
X
Temperature of
device interior
Temperature > threshold 1
X
-
X
-
-
Temperature > switch-off threshold
-
X
-
-
X
Motor temperature
I
2
t threshold exceeded
-
X
X
-
X
Threshold 1 exceeded
2)
X
-
X
-
-
Threshold 2 exceeded
2)
X
-
X
-
-
Sensor short-circuit and/or
temperature < -30 °C
2)
-
X
-
-
-
Sensor not connected and/or
temperature > 250 °C
2)
-
X
-
-
-
Maximum temperature exceeded
2)
-
X
X
-
X
Position controller
Dynamic position deviation
-
X
X
X
-
Static position deviation
-
X
X
X
-
Encoder 1
Cable break
-
X
X
X
-
Cable break (SIN
2
+ COS
2
)
-
X
X
X
-
Excessive rotational speed
-
X
X
X
3)
1)
Pulse inhibit carried out after a set time interval
2)
Only if KTY/PT1000 sensor used
3)
Adjustable
X: Implemented
-: Not possible