Parameter
Parameter manual
b maXX
®
1000
Document no. 5.07004.03
143
4
P2072
Display the signal of AO2 analog output [mA or V].
4095 Inc
⇔
20.0 mA or 10.0 V
0 - 4095 Inc
⇔
0.0 - 20.0 mA or 0.0 - 10.0 V
P2073
Display the speed actual value in rpm.
P2080
The coefficient K determines the multiplying factor for the user-defined unit.
The display value is calculated as follows:
U (User-defined unit) = Actual output frequency * K
Example:
A conveyor belt runs at 13.6 m/s at motor speed 60 Hz.
K = 13.6/60 = 0.22 (0.226667 rounded to 1 decimal), therefore
= 0.2
With Frequency command 35 Hz, display shows U and 35
⋅
0.2 = 7.0 m/s.
(To increase accuracy, use K = 2.2 or K = 22.7 and disregard decimal point)
P2081
and
are used to record the motor operation time. They can be
cleared by setting to 0 and time is less than 1 minute is not recorded.
P2072
Anzeige AO2 analoger Ausgang
0 to 65535
-
Display of AO2 analog output
0
A
BM_u_AO2AnalogOutput
1:1
-
P2073
Anzeige Geschwindigkeits-Istwert in U/min
0 to 36000 rpm
-
Display speed actual value in rpm
0 rpm
A
BM_u_DisplaySpeedActValue
1:1
-
P2080
Benutzerdefinierter Faktor K
0.1 to 160.0
EE
User defined coefficient K
1.0
ON
BM_u_UserDefinedCoeffK
10:1
P2081
Motorbetriebszeit (Minuten)
0 to 1439
-
Accumulative motor operation time (min)
0
A
BM_u_AccumulMotorOperationTimeMin
1:1
Содержание b maXX 1000
Страница 1: ...E 5 07004 03 b maXX 1000 Parameter manual ...
Страница 65: ...Parameter Parameter manual b maXX 1000 Document no 5 07004 03 65 of 208 4 Figure 18 Base block speed search ...
Страница 164: ...Parameter manual b maXX 1000 Document no 5 07004 03 Baumüller Nürnberg GmbH 164 of 208 A ...
Страница 208: ...Parameter manual b maXX 1000 Document no 5 07004 03 Baumüller Nürnberg GmbH 208 of 208 Notes ...
Страница 209: ......