![Baumuller b maXX 1000 Скачать руководство пользователя страница 132](http://html.mh-extra.com/html/baumuller/b-maxx-1000/b-maxx-1000_parameter-manual_2711401132.webp)
Parameter description
Parameter manual
b maXX
®
1000
Document no. 5.07004.03
Baumüller Nürnberg GmbH
132
4.3
P1364
This parameter defines an upper bound or limit for the integral gain (I) and therefore limits
the master frequency.
The formula is:
Integral upper bound = maximum output frequency
x
.
This parameter can limit the maximum output frequency.
P1365
To avoid amplification of measurement noise in the controller output, a derivative digital
filter is inserted. This filter helps to dampen oscillations.
P1366
This parameter defines the percentage of output frequency limit during the PID control.
The formula is:
Output frequency limit = maximum output frequency
This parameter will limit the maximum output frequency. An overall limit for the output fre-
quency can be set in
.
P1364
Obere Grenze Integralverstärkung
0 to 100 %
EE
Upper bound for integral control
100 %
STOP
BM_u_UpperBoundIntegralControl
1:1
-
P1365
Hauptfilter Verzögerungszeit
0.0 to 2.5 s
EE
Primary delay filter time
0.0 s
STOP
BM_u_PrimaryDelayFilterTime
10:1
-
P1366
Ausgangsfrequenz Grenze
0 to 110 %
EE
Output frequency limit
100 %
STOP
BM_u_OutputFrequencyLimit
1:1
-
Содержание b maXX 1000
Страница 1: ...E 5 07004 03 b maXX 1000 Parameter manual ...
Страница 65: ...Parameter Parameter manual b maXX 1000 Document no 5 07004 03 65 of 208 4 Figure 18 Base block speed search ...
Страница 164: ...Parameter manual b maXX 1000 Document no 5 07004 03 Baumüller Nürnberg GmbH 164 of 208 A ...
Страница 208: ...Parameter manual b maXX 1000 Document no 5 07004 03 Baumüller Nürnberg GmbH 208 of 208 Notes ...
Страница 209: ......