Parameter description
Parameter manual
b maXX
®
1000
Document no. 5.07004.03
Baumüller Nürnberg GmbH
118
4.3
P1186
Set for all RFG accel/decel times the time unit.
The ramp are selected according to the multi-function input terminals settings. See
for more details.
In the diagram shown below, the acceleration/deceleration time of the b maXX
®
1000 is
the time between 0 Hz to maximum output frequency
. Suppose the maximum
output frequency is 60 Hz, minimum output frequency
is 1.0 Hz, and accelera-
tion/deceleration time is 10 seconds. The actual time for the b maXX
®
1000 to accelerate
from start-up to 60 Hz and to decelerate from 60 Hz to 1.0 Hz is in this case 9.83 s
((60-1) * 10/60=9.83 s).
Figure 52:
Resulting accel/decel time
P1186
RFG Hochlauf/Rücklauf Zeiteinheit
0 to 1
EE
RFG accel/decel time unit
0
STOP
BM_u_AccelDecelTimeUnit
1:1
Value
Meaning
0
Unit: 0.1 s
1
Unit: 0.01 s