Commissioning/Operation
Instruction handbook
b maXX
(BM4-F-)AIO-XX (Analog IO module)
Document No.: 5.01045.08
51
8
5
Check the display in „Analog input link 1“.
The RPM of the motor can be regulated now by potentiometer for instance within limits
-10 V and +10 V (clockwise and counter-clockwise running).
6
Repeat the above steps for the input 2.
8.2.2.2 Testing of inputs AIO-04
1
ProDrive Navigation „IO analog inputs“.
2
Select „Analog input link 1“ in ProDrive.
Figure 17:
Analog input link 1, AIO-04
NOTE!
If for example, the scale shows 0 V, even though there is an analog voltage applied
on input 1 (see pin assignment
on page 39), then the input
is defective. When changing the analog input voltage, the relevant value of the volt-
age must be displayed on the scale.