Functions
|
8
V2 | OM20/OM30 IO-Link
Operating Manual
35
Window mode (switching output behavior)
Positive hysteresis:
High
Low
Level
Hysteresis
Switching point P2
Active high level
Switching point P1
Hysteresis
Window
Ill. 18:
Behavior of the switching output in window mode (positive hysteresis)
Negative hysteresis:
High
Low
Level
Hysteresis
Switching point P2
Active high level
Switching point P1
Hysteresis
Window
Ill. 19:
Behavior of the switching output in window mode (negative hysteresis)
IO-Link parameter: Hysteresis
Parameter name
Values
Description
Hysteresis.SSC1 Width
-
Enter the hysteresis as a positive or negative nu-
merical value (in mm).
8.9
Function of the output
The IO-Link communication principle can also be used as a switching output. In the factory set-
tings, the function of the output is equivalent to the alarm output. This means that the output is
activated as soon as no measured value can be recorded. Through IO-Link this can be switched
to a switching output than can be parameterized.