4.3
Configuration - Switching Signal Channel (SSC)
The sensor features two different switching channels. Switching Signal Channel SSC1 is reserved for object
detection.
Switching Channel 4 includes a counter function with an auto-reset. All switching channels can be adjusted
individually via IO-Link. All switching channels can be mapped to the MDC as well. Then they will show the
counts detected by the channel.
For more information about how to set-up the Counter/SSC4 channel and its behavior, please see section
4.3.4.
4.3.1
Setpoints SP
Using this parameter the user can modify the switchpoint of the sensor by enter the intensity (O200.R) or
distance value (O200.G, O200.S) at which the sensor should switch (teach-by-value function).
shows the illustration of the switching behavior. Regarding Single point mode only SP1 is relevant, SP2 is
not active.
For the Window mode SP1 & SP2 are active. The switching modes are explained in section
Window mode is only available for the SSC1 of O200.G and for the SSC4/Counter.
Figure 4
Single Point Mode (O200.R, O200.G)
SP1: Switch point 1
SP2: Not active
Figure 5
Window Mode (Only O200.G or SSC4)
SP1: Switch point 1
SP2: Switch point 2
Figure 6
Single Point Mode (O200.S)
SP1: Reference/backgroundposition
Parameter name
Short Description
Rights
Unit /
Allowed
values
SSC1 Param.SP1
Defines the value at which the related SSC is set to active (or
inactive if inverted) or the position of the reference (O200.S)
rw
SSC1 Param.SP2
(Only O200.G)
Defines the value at which the related SSC is set to inactive (or
active if inverted)
-
only active if SSC is set to window mode
rw
SSC1
Param.Background
Tolerance
Only available for O200.S
This value in % states the relative allowable variance of the
reference position. (+/-)
rw
%